Manual – MOVI-PLC® advanced Controller Remote Maintenance via ORA11B
33
5
Establishing a connection on the engineering PC
Configuration
Select the "SMLP settings" "1" tab. In the "Basic settings" group box, in the input field
"Broadcast IP Address" [2], enter the IP address of MOVI-PLC
®
advanced
(see follow-
ing figure).
As a result, the MOVI-PLC
®
advanced
is also found in the online scan and the PLC
Editor can be started as usual.
64003AEN
[1]
[2]
NOTES
To establish a stable connection, you probably have to increase the timeout settings
in MOVITOOLS
®
MotionStudio and in the PLC Editor. The timeout settings are avail-
able in the menu items:
• MOVITOOLS
®
MotionStudio:
– [Settings] / [Options] / [Communication timeout]
Proposal: 15000 ms
– [Network] / [Configure communication connections] / [Ethernet] / [SMLP set-
tings]
Proposal: 10000 ms
• PLC Editor:
– [Project] / [Work area]
Proposal: 8000 ms
These (suggested) timeout settings prevent that a timeout of higher level becomes ef-
fective before a timeout of a lower level.