Manual – MOVITRAC® B Communication Interface FSE24B EtherCAT®
4
Status LEDs of FSE24B
Assembly and Installation Notes
4.7.1
LED RUN (green)
The
RUN
LED (green) indicates the status of the FSE24B communication option.
4.7.2
LED ERR (red)
The LED
ERR
(red) indicates an EtherCAT
®
error.
Condition
State
Description
Off
INIT
Option FSE24B communication option is in the state INIT.
Flashing
PRE-OPERATIONAL
Mailbox communication is possible but no process data
communication
Flashing once
SAFE-OPERATIONAL
Mailbox and process data communication is possible. The
slave outputs are not output yet.
On
OPERATIONAL
Mailbox and process data communication is possible.
Condition
Error
Description
Off
No error
The EtherCAT
®
communication of FSE24B is in the operat-
ing state.
Flickering
Boot error
A boot error was detected. The state INIT was achieved, but
the "Change" parameter in the AL status register has been
set to "0x01:change/error".
Flashing
Invalid configuration
General configuration error.
Flashing once
Unprompted state
change
The slave application has changed the EtherCAT
®
state
automatically. The "Change" parameter in the AL state regis-
ter is set to "0x01:change/error".
Flashing twice
Timeout of the appli-
cation watchdog
A watchdog timeout has occurred in the application.
Flashing three
times
Reserved
-
Flashing four
times
Reserved
-
On
PDI watchdog timeout A PDI watchdog timeout occurred.