Project planning
Operation with reduced supply voltage
Operating Instructions – Compact Extra-Low Voltage Drives
86
12.5.3
Parameter adjustment prior to startup
CAUTION
Danger due to:
- Unsuitable parameterization for operation with reduced supply voltage.
- Increased voltage in regenerative operation.
- Fluctuating supply voltage, e.g. with battery supply.
Potential damage to property
• Adhere to the changed values in the parameter table. Parameterize only permit-
ted values.
For operation with supply voltage, e.g.
DC 24
V, you must change the factory setting
of the following parameters:
No. Parameter
Unit
Setting
Min.
Max.
Class
Explanation
0x4A U
DC48V
overvoltage
threshold
mV
29000
0
65535 System
Overvoltage > 29 V
0x4B U
DC48V
under-
voltage threshold
mV
18000
0
65535 System
Undervoltage < 18 V
0x4C U
DC48V
voltage hys-
teresis
mV
2000
0
65535 System
Hysteresis for
voltage signal
0x4D Ballast chopper
switch-on
threshold
mV
28000
0
65535 System
Brake chopper
switch-on threshold
0x4E Ballast chopper
switch-off
threshold
mV
27000
0
65535 System
Brake chopper
switch-off threshold
For the parameters fixed speed N1, fixed speed N2, fixed speed N3, fixed speed N4
and max. positioning speed, you may parameterize only values up to 2000 min
-1
.
No. Parameters
Unit
Setting
Min.
Max.
Class
Explanation
0x17 Fixed speed N1
min
-1
1000
0
29999 Application
Fixed speed N1
0x18 Fixed speed N2
min
-1
2000
0
29999 Application
Fixed speed N2
0x19 Fixed speed N3
min
-1
2000
0
29999 Application
Fixed speed N3
-
Fixed speed N4
min
-1
500
0
29999 Application
Fixed speed N4
0x3F Max. positioning
speed
min
-1
2000
0
29999 Application
Max. speed for posi-
tioning mode
26718014/EN – 11/2020