LINEAR OPTICAL REFLECTING BEAM  SMOKE DETECTOR

 

 

 

S

 6P150 

distance: min 71m to max 150m

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

VARIABLE POSITIONING RELATIVE TO THE PLANE THE BRACKET IS FASTENED ON AND 

MICROMECHANICAL REFLECTOR DEVICE 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

ATTENTION 

 

MODEL REQUIRES INTERFACE INT8BA 

Before installing the detectors, check the wall or surfaces on which the TRX brackets and micromechanical reflector 
device are mounted. They must not be in any way subjected to movement or vibrations during the operation of the 
units. 
Before installing the units check whether there are any shiny or reflective surfaces crosswise between the beams 
along the IR beam path between the TRX and the micromechanical reflector device. If there are, check whether they 
interfere with the micromechanical reflector response. If a part of IR light is reflected back by surfaces other than this 
reflector device, different  TRX positions should be selected.  
Do not place this model of detector in warehouses where the goods stored are closer than 1,20m to the ceiling or 
roof. Keep the whole path whole detector path  distance between the TRX and reflector device as clear as possible. 
Avoid detector placement in front of or near to strong electric lights or bright sunlight. 
If there are particularly problematic situations, one or more reflector device may be required and a diaphragm could 
also be required as an additional accessory to be used according to the instructions provided. 

RILEVAZIONE ELETTRONICA ANTINCENDIO 

37138 VERONA - Via F. Da Levanto 14 - b 

Tel. +39 - 0458347777    Fax +39 - 0458347778 

E-mail: [email protected] 

www.setronicverona.com 

150m MAX 

)

 

)

 

)

 

)

 

)

 

TRX 

STRxBS 

Micromechanical 

Reflector Device 

SRFxBS150 

126 mm 

178 m

m

 

148 m

m

 

220 mm 

Содержание Boomerang S 6P150

Страница 1: ... reflector response If a part of IR light is reflected back by surfaces other than this reflector device different TRX positions should be selected Do not place this model of detector in warehouses where the goods stored are closer than 1 20m to the ceiling or roof Keep the whole path whole detector path distance between the TRX and reflector device as clear as possible Avoid detector placement in...

Страница 2: ...g and goes out Counting the number of turns of the knob turn back to the left side turning and counting until the yel low led stops flashing and goes out During operation the Smoke red flashing led can light up in alarm mode This is normal Reset by removing the connector to the TRX for min 3 seconds 6 Divide the number of turns two and turn by that amount towards the middle You have now found the ...

Страница 3: ...uc tions given in c above Threshold values over 1000 are not suggested unless you have first con sulted with out authorised services e Switch OFF and disconnect the UTA Jack plug store the instrument in a cool dry place without its batteries CALIBRATION PROVIDED BY ADM DEVICE AND MULTIMETER If an ADM is being used a Insert the ADM jack plug in the TRX socket Switch on ADM and select detector mode ...

Страница 4: ...ON 2 Delay 30 POSITION 3 Delay 60 POSITION 4 Delay 90 1 2 3 4 5 6 7 8 24V GND NO C NC NO C NC TERMINALS NOT USED IN BOOME RANG MODELS 104 mm 130 mm 104 mm 130 mm inserted not inserted ABSORBTION MAX 24 VOLT interface included mA MAX JB IN JB OUT NORMAL WORKING 65 78 TROUBLE 87 72 ALARM 78 91 RRX www setronicverona com LINE LINE ...