Multi-Sense
®
Model 231
Multi-Configurable, Wet-to-Wet Differential Pressure Transducer
ORDERING INFORMATION
Model
Range Specifications
1
Pressure Connection
Display
231G = 231
Unidirectional
Bidirectional
2F 1/8-18 NPT female (Standard) Sensor
(Conduit Version)
N
No Display
MS1
5, 10, 25, 50 PSID
±5, ±10, ±25, ±50 PSID
3V 3-V Manifold assembled w/ Model 231
D
LCD Display
MS2
10, 20, 50, 100 PSID
±10, ±20, ±50, ±100 PSID
5V 5-V Manifold assembled w/ Model 231
MS3
25, 50, 125, 250 PSID
±25, ±50, ±125, ±250 PSID
1
Maximum line pressure is maximum range
of pressure ordered.
2 3 1 G
Ordering Example: 231GMS12FD = Model 231, 5 PSID up to 50 PSID, 1/8” NPT Int. Fitting, and LCD Display 31GMS13VN= Model 231, 0 to 5 PSID up to 50
PSI, 3-Valve Manifold, and No LCD Display
Valve A
1
High
Low Pressure
Remote Sensor
High Pressure
Remote Sensor
Valve B
1
Low
Valve A = High Side Valve
Valve B = Low Side Valve
1. Valves not included.
Examine the pressure application and determine what is the Highest System Line Pressure.
Determine what is the Differential Pressure being measured.
Find the MAX. Line Pressure in the table on the right that is > to your Highest System Line Pressure.
Verify that your DP falls within the selectable ranges in that row.
Follow that row to the left and select that range code.
Example:
Highest System Line Pressure: 125 PSIG
Differential Pressure Measured: 50 PSID
“Max Line Pressure” ≥ to System Line Pressure: 250 PSID (50 PSID DP falls within ranges in this row)
Select Range Code: MS3
Range
Code
A
B
C
D
Max. Line
Pressure
MS1
50
25
10
5
50
MS2
100
50
20
10
100
MS3
250
125
50
25
250
Pipe
Pipe
INSTALLATION
PRESSURE RANGE CODE SELECTOR (IMPORTANT: READ BEFORE ORDERING)
Model 231