Gateway MODBUS-to-Opentherm MB-OTG 

Technical manual

 

The mapping between Register/Coil and OpenTherm function is the following: 

Readable Modbus Registers 

 (by using MODbus function 0x03) 

Corresponding 

Opentherm ID 

Format 

Register Number (address) 

NOTES 

 

 

 

 

 

Slave Config 

 

 

Fault Flag (OEM Fault Code) 

 

 

RBP Flags 

 

 

Maximum  boiler  capacity  (kW)  / 
Minimum Modulation Level (%) 

15 

 

 

Relative Modulation Level (%) 

17 

tenth of % 

 

Water Pressure in CH Circuit (bar) 

18 

tenth of bar 

 

Boiler Flow Water Temperature (°C) 

25 

tenth of °C 

 

DHW Temperature (°C) 

26 

tenth of °C 

 

Outside Temperature (°C) 

27 

tenth of °C 

10 

 

Return Water Temperature (°C) 

28 

tenth of °C 

11 

 

Boiler Exhaust Temperature (°C) 

33 

tenth of °C 

12 

 

Boiler Fan Speed Setpoint and Actual 
Value 

35 

 

13 

 

Electrical  current  through  burner 
flame (uA) 

36 

 

14 

 

DHW Setpoint bounds 

48 

tenth of °C 

15 

 

CH Setpoint bounds 

49 

tenth of °C 

16 

 

Burner operation hours 

120 

integer number 

17 

 

CH Pump operation hours 

121 

integer number 

18 

 

 

 

 

 

 

Number  of  Communication  Error  on 
Opentherm side 

n/a 

integer number 

22 

 

Opentherm communication failed 

n/a 

If=1, 
communication KO 

23 

 

 

 

 

 

 

Writable MODbus register 
(by using MODbus function 0x05) 

 

 

 

 

 

 

 

 

 

CH Water temperature setpoint 

tenth of °C 

25 

 

DHW Setpoint 

56 

tenth of °C 

26 

 

Maximum  relative  modulation  level 
setting 

14 

tenth of % 

27 

 

 

 

 

 

 

Readable Coils 
(by using MODbus function 0x01) 

Bit of Opentherm ID 0 

 

Coil Number (address) 

 

 

 

 

 

 

Fault indication 

0 (reading) 

 

 

CH Mode 

1 (reading) 

 

 

DHW Mode 

2 (reading) 

 

 

Flame Status 

3 (reading) 

 

 

 

 

 

 

 

Writable Coils 
(by using MODbus function 0x05) 

 

 

 

 

CH Enable 

0 (writing) 

 

48 

 

DHW Enable 

1 (writing) 

 

49 

 

 

 

Содержание MB-OTG

Страница 1: ...ited without an express written authorization SETECNA S r l Via A Volta 19 B 37062 Dossobuono di Villafranca di Verona VERONA P IVA 03200030231 SETECNA ss S r l Rev 01 Alessandro Page 1 di 10 14 09 20...

Страница 2: ...ERONA P IVA 03200030231 SETECNA ss S r l Rev 01 Alessandro Page 2 di 10 14 09 2016 23 09 16 17 56 Gateway MODBUS to Opentherm MB OTG Technical manual Table of Contents 1 Introduction 3 2 Installation...

Страница 3: ...MODbus protocol PLCs Industrial PCs SCADA systems ecc with Boilers sometimes in this manual it is used the annotation Blr that use OpenTherm protocol Every gateway is assigned a MODbus address by a ro...

Страница 4: ...annel is optoisolated from the MODbus side MODbus interface is not optoisolated respect to the Gateway s Power Supply so typically the Master and Gateway are powered by the same Power Supply or from P...

Страница 5: ...ges according to the position assumed by the rotative switch with 16 positions on the device The rotary switch is placed under the plastic case to open it you have to apply a light pressure with a sma...

Страница 6: ...nctions On the Gateway s front panel there are some leds that show the functioning state of the device LED STATUS MEANING BUS green ON Gateway correctly Powered BUS green Blinking Writing Reading data...

Страница 7: ...m protocol Mapping The Gateway maps the exchanged informations some information read other written with the Boiler in as many Register or Coils of the MODbus protocol In particular the Gateway recogni...

Страница 8: ...Temperature C 25 tenth of C 8 DHW Temperature C 26 tenth of C 9 Outside Temperature C 27 tenth of C 10 Return Water Temperature C 28 tenth of C 11 Boiler Exhaust Temperature C 33 tenth of C 12 Boiler...

Страница 9: ...ow temperature setpoint of the Boiler on 55 C set to 550 the holding register number 25 To set the power limit to 70 for the Boiler set to 700 the holding register number 27 Attention To control the t...

Страница 10: ...way receive a valid command from the MODbus In presence of Communication errors first check if the LED BUS turns on if the MODbus communication is frequent the led will be always on on the contrary if...

Отзывы: