Setec ST20-II Скачать руководство пользователя страница 11

ST – II Series POWER SUPPLIES

USER INSTRUCTIONS

Electromagnetic compatibility (EMC)

Electromagnetic compatibility (EMC) is defined as “the ability of a device, equipment or system to 
function satisfactorily in its electromagnetic environment without introducing intolerable 
electromagnetic disturbance to anything in that environment”.
Switch-mode power supplies are good generators of EMI and as such care needs to taken during 
their designs to limit their emissions. Requirements of the local regulator (ACA) limit the emissions 
to protect the frequency spectrum. Limits are set down in standards such as EN55022 for radiated 
and conducted emissions. However, these limits are not satisfactory for devices in close proximity 
(<3m) and as such do not guarantee that the power supply will not cause interference with devices 
such as TV’s or radios.
The ST20-II/35-II have been designed with equipment interoperability in mind. The emissions are 
in the order of 10 – 100 times below the regulator requirements (this is expressed in dB (µV)) and 
greatly reduce the likelihood of causing interference with Radios and TV’s located in close 
proximity.

However, care still needs to be taken with the routing of cables and placement of the unit with 
respect to appliances. Small emissions can still cause interference. 

If interference is present, then 

locate cables from the power supply away from appliance so far as possible and also locate the  
power supply away as far as practical.

Page 11 of 11

Issue F

5MH

z

0.15MH

z

30MH

z

AM Band

30dB

 

Margin

EN55022 Class B Limit

ST20-II/35-II Conducted Emissions

Содержание ST20-II

Страница 1: ...of the load from an external 13 8V DC power source The units are fully enclosed ready for direct wall mounting All connections are at the rear of unit providing convenient wiring and installation Use...

Страница 2: ...battery will be charging at 0 8A When the battery voltage is sufficient 10 5V for first power up 11 5V and 11 7V for subsequent reconnection with and without mains respectively the LVD will connect th...

Страница 3: ...ll shut down It will attempt to automatically restart every 5 seconds until such case that the fault is removed Fusing Each load circuit and the battery have been fused to provide fault protection and...

Страница 4: ...shut down A minimum ventilation of 20 000mm2 to the outside world must be provided CAUTION Do not install unit in same compartment as batteries or flammable material such as petrol Ensure that the ins...

Страница 5: ...ating QC connector suitable for cable size Connector pin out is shown below Cabling sizes DC cables must be sized to carry the maximum full load current and not exceed the system volt drop requirement...

Страница 6: ...r supply terminal or negative chassis ground If battery is connected to chassis ensure a connection exist from chassis to Batt VE terminal of power supply Battery Disconnection Procedures Battery shou...

Страница 7: ...servicing a battery disconnect the power supply Batteries are electrically alive at all times and must be treated with extreme caution They can supply high short circuit currents even if they appear d...

Страница 8: ...tion 17V Over Current Protection ST20 II 20A to 25A load battery current ST35 II 35A to 38A load battery current Battery Current Limit 10A 1A ST20 II 15A 1A ST35 II Battery Connect Disconnect Connect...

Страница 9: ...A detailed description of the operational requirements for the charging algorithm is described below Present Output Set Voltage Conditions Required to Enter Operational State Operational State New Ou...

Страница 10: ...oost charging mode active after resumption of mains input supply set 15 minute boost timer Vboost Vboost No mains input voltage is detected Boost charging mode while no mains is detected Vboost No Mai...

Страница 11: ...or devices in close proximity 3m and as such do not guarantee that the power supply will not cause interference with devices such as TV s or radios The ST20 II 35 II have been designed with equipment...