Setec ST - III Series Скачать руководство пользователя страница 3

ST–III Series Power Supplies

USER INSTRUCTIONS

3. Flashing 1s ON, 1s OFF, with no battery connected the power supply may be in hiccup 

mode which will cause the indication to flash with random duty cycle and frequency.

4. Fault Led= Solid On, All other leds = OFF, irrespective of actual mains or LVD status.

Auxiliary Power Input: 

The power supply terminal “Aux In +VE” provides an alternative option 

for powering of the load and float charging of the batteries when mains voltages are not present. 
This input is to be powered by a suitable  +12V system. (i.e. CAR).  The voltage of the auxiliary 
power source should not exceed 14.8 volts.
When operating via the external input, current and voltage control for the battery must be provided 
from the external source. The ST20-II/35-II does not provide battery current limit or voltage control 
when operating in this configuration.  Trickle Charge is still functional when powered through 
“Aux In +VE” terminal of power supply.
Suitable fuse protection must be provided for this input.  A fuse rating not exceeding 20 Amps for 
ST20-II and 30 Amps for ST35-II must be used.
Solar power should be connected directly across the battery terminals with a voltage regulator in 
series.  A solar panel voltage regulator with maximum output voltage not exceeding 14.8 volts must 
be used at all times.  Failure to use a voltage regulator may result in power supply damage.
Generator 12 volt outputs should not be connected across battery terminal whilst battery is 
connected to power supply or connected to the “Aux In +VE” terminal of power supply.  Serious 
power supply damage or internal explosion may occur.  If a flat 12 volt battery has to be charged 
using the generators 12 volt output, it should first be disconnected from the power supply.  Once 
battery has being charged it can then be reconnected to power supply.
Power supply unit should only be powered from either 240VAC mains or Auxiliary Power 
(Auxiliary Power also includes solar power) but 

not both

.  Failure to do so may result in damage to 

power supply. 

Protection: 

the power supply provides automatic protection for overload including short circuit, 

over-voltage, over-temperature and reverse connected battery. In such instances the Fault indicator 
will illuminate and the power supply will shut down. It will attempt to automatically restart every 5 
seconds until such case that the fault is removed.

Fusing: 

Each load circuit and the battery have been fused to provide fault protection and 

discrimination. Refer to servicing section for maximum fuse ratings. 

CAUTION:

This appliance is 

not

 intended for use by young children or infirm persons without supervision.

Young children should be supervised to ensure that they do not play with the appliance.
In order to avoid hazard when the supply cord becomes damaged, the cord must only be replaced by 
the manufacturer or its service agent or similar technically qualified person.
Power supply unit should only be powered from either 240VAC mains or Auxiliary Power 
(Auxiliary Power also includes solar power) but not both.  Failure to do so may result in damage to 
power supply.

Page 3 of 11

Issue D

Содержание ST - III Series

Страница 1: ...ear of unit providing convenient wiring and installation User access to all load and battery fusing has been provided from the front of the unit Operation Safety Refer to the installation section befo...

Страница 2: ...ccurs when battery voltage recovers Battery Current Drain is less than 2mA Trickle Charge to the battery is always present When the battery voltage is below the LVD Low voltage disconnect re connect v...

Страница 3: ...l whilst battery is connected to power supply or connected to the Aux In VE terminal of power supply Serious power supply damage or internal explosion may occur If a flat 12 volt battery has to be cha...

Страница 4: ...shut down A minimum ventilation of 20 000mm2 to the outside world must be provided CAUTION Do not install unit in same compartment as batteries or flammable material such as petrol Ensure that the ins...

Страница 5: ...xternal DC Input Connections Connectors are 0 8 x 6 3mm QC tabs Use mating QC connector suitable for cable size Connector pin out is shown below Page 5 of 11 Issue D F4 F5 F6 F7 F8 FBATT L1 L2 L3 L4 L...

Страница 6: ...al of power supply Battery Disconnection Procedures Battery should be disconnected as per the following steps Turn power supply off and all 12 volt equipment connected to power supply Disconnect negat...

Страница 7: ...cell does not cause short circuits Remove any personal metal adornment such as a chain watch or ring which could cause short circuits and personal injury Do not charge non rechargeable batteries Failu...

Страница 8: ...r Current Protection ST20 II 20A to 25A load battery current ST35 II 35A to 38A load battery current Battery Current Limit 10A 1A ST20 II 15A 1A ST35 II Battery Connect Disconnect Connect 10 50 0 2V I...

Страница 9: ...d A detailed description of the operational requirements for the charging algorithm is described below Present Output Set Voltage Conditions Required to Enter Operational State Operational State New O...

Страница 10: ...boost charging mode active after resumption of mains input supply set 15 minute boost timer Vboost Vboost No mains input voltage is detected Boost charging mode while no mains is detected Vboost No Ma...

Страница 11: ...r devices in close proximity 3m and as such do not guarantee that the power supply will not cause interference with devices such as TV s or radios The ST20 III 35 III have been designed with equipment...

Отзывы: