20
SESAMO
DUALCORE
WARNING:
the sensor on the exit way side (sensor B - figure 4) must be IXIO DT3 model
- set in radar mode "current" output and connected as shown in the diagram fig.25
WARNING:
the jumpers between terminals 3 and 4 of the Master and Slave boards
must be removed.
WARNING
Proceed with commissioning following the instructions in the
Commissioning
paragraph. Operate only on the Master control unit for commissioning.
TERMINAL BOARD CONNECTIONS EN
16005
Connect all parts of the automatic doorway to the Dualcore processor with suitably sized
cables, in accordance with the indications in the table below:
N
Ref.
Default
Description
Figure
1
START1
NO
external sensor for opening control
Fig.24/25/25A/26
2
COM
Standard signal: for inputs 1 and 5 in
the LH100/LH140 versions - only for
input 1 in the RD100 version
3
OPTOREF
For LH100/LH140 versions jumper -
For RD100 version remove the
jumpers and connect as shown in the
diagram fig.25
4
-OO-
5
START2
NO
internal sensor for opening control
6
OUT 15VDC
(-)
Power supply negative for internal
external opening control sensors:
15Vdc
–
max. 0,25A
7
OUT 15VDC
(+)
Power supply positive for internal
external opening control sensors:
15Vdc
–
max. 0,25A
8
TEST CLOSE
(-)
negative test circuit of the
internal/external sensor
Fig.24/25/26/29
9
TEST CLOSE
(+)
positive test circuit of the
internal/external sensor
10
COM
standard signal for input: 11, 13
11
SAFE CLOSE 1
NC
Area A2 external presence sensor
active safety
12
PHOTO COM
Disposition not to use
13
SAFE CLOSE 2
NC
Area A1 internal presence sensor
active safety
14
TEST OPEN
(-)
negative test circuit of the right/left
side opening safety sensor
Fig.27/28/29
15
TEST OPEN
(+)
positive test circuit of the right/left
side opening safety sensor
Содержание DUALCORE LH100
Страница 1: ...LH100 LH140 RD100 ENGLISH AUTOMATED SYSTEMS FOR SLIDING DOORS INSTALLATION MANUAL ...
Страница 44: ...44 SESAMO DUALCORE Fig A Fig B ...
Страница 45: ...45 SESAMO DUALCORE Fig 1 ...
Страница 46: ...46 SESAMO DUALCORE Fig 2 ...
Страница 47: ...47 SESAMO DUALCORE Fig 3 ...
Страница 48: ...48 SESAMO DUALCORE WARNING Exit way ONLY for RD100 Fig 4 ...
Страница 49: ...49 SESAMO DUALCORE Fig 5 ...
Страница 50: ...50 SESAMO DUALCORE Fig 5 A ...
Страница 51: ...51 SESAMO DUALCORE Fig 6 Fig 7 ...
Страница 52: ...52 SESAMO DUALCORE Fig 8 Fig 9 ...
Страница 53: ...53 SESAMO DUALCORE Fig 9a Fig 10 ...
Страница 54: ...54 SESAMO DUALCORE Fig 11 Fig 12 ...
Страница 55: ...55 SESAMO DUALCORE Fig 13 Fig 14 Fig 15 ...
Страница 56: ...56 SESAMO DUALCORE Fig 16 Fig 16a ...
Страница 57: ...57 SESAMO DUALCORE Fig 17 Fig 17a ...
Страница 58: ...58 SESAMO DUALCORE Fig 18 Fig 19 Fig 20 ...
Страница 59: ...59 SESAMO DUALCORE Fig 21 Fuses 6 3A T J ...
Страница 60: ...60 SESAMO DUALCORE Fig 22 ...
Страница 61: ...61 SESAMO DUALCORE Fig 23 1 Fig 23 2 ...
Страница 62: ...62 SESAMO DUALCORE Fig 24 PARAMETER 30 1 ...
Страница 63: ...63 SESAMO DUALCORE Fig 25 PARAMETER 30 1 Exit way ...
Страница 64: ...64 SESAMO DUALCORE Fig 25 A ...
Страница 65: ...65 SESAMO DUALCORE Fig 26 ...
Страница 66: ...66 SESAMO DUALCORE Fig 27 PARAMETER 31 1 ...
Страница 67: ...67 SESAMO DUALCORE Fig 28 PARAMETER 31 0 ...
Страница 68: ...68 SESAMO DUALCORE Fig 29 ...
Страница 69: ...69 SESAMO DUALCORE Fig 30 Fig 31 ...
Страница 71: ...71 SESAMO DUALCORE Fig 33 ...
Страница 72: ...72 SESAMO DUALCORE Fig 34 ...