M – Basic Maintenance
OMM.M.S.ZZ.00
M-
3
June
2018
Specific Components Maintenance
Actual maintenance plan may vary from installation to installation, yet there are several key components from
maintenance prospective.
If needed, contact respective component manufacturer for additional maintenance information.
Filters
Ensure air filters are clean. Dirty air filters will negatively affect dehumidifier performance and lifetime
Frequency of filters replacement will vary based on air quality, dehumidifier usage, facility type, etc. Make
sure to replace filters regularly
Replace with filters of equivalent size and rating – refer to dehumidifier details (compartment stickers, etc.)
Insulation
Inspect dehumidifier insulation, exposed to airstream for microbial growth (i.e., mold). If there is evidence of
microbial growth on the interior insulation, the insulation should be removed and replaced prior to operating the
dehumidifier.
Air-Side Coils
Warning: Hazardous chemicals!
Cleaning agents can be highly acidic or alkaline. Handle all chemicals carefully
and use appropriate personal protective equipment (PPE). Refer to the cleaning agent manufacturer's Materials
Safety Data Sheet (MSDS) for safety and handling information. Failure to follow all safety instructions could
result in serious injury or death.
Warning: Hazardous pressures!
Coils containing refrigerant under pressure must not be cleaned using a
solution over 150 ºF. Failure to follow these safety precautions could result in coil bursting, which could result
in serious injury or death.
To clean the coil
Disconnect all electrical power to the equipment
Use a soft brush to remove loose debris from the coil
Mix a high-quality coil cleaning detergent with water according to the manufacturer's instructions
Clean coil according to suggested instructions
Thoroughly rinse both sides of the coil and the drain pan with, clean water
Straighten any coil fins that have been bent during the cleaning process
Confirm the drain line is clear
Replace all panels and parts and restore electrical power to the equipment
Содержание CLASSIC NE Series
Страница 3: ...B Table of Content B 2 This page is left blank...
Страница 11: ...C General Information C 8 This page is left blank...
Страница 17: ...D Layout and Components D 6 This page is left blank...
Страница 21: ...E Sequence of Operation E 4 This page is left blank...
Страница 25: ...F Interface and Communication F 4 This page is left blank...