SEPLOS PUSUNG 2
ND
GENERATION 51.2V 100AH LIFEPO4 BATTERY PACK USER MANUAL
www.seplos.com
4
BMS has over-discharge, over-charge, over-current, high and low temperature warning and
protection functions.
BMS monitors charge and discharge state, and balance current and voltage of each cell.
BMS comes with upper computer system for real-time cell and pack voltage, current,
temperature, and battery status monitoring and recording.
Flexible configuration, max. 15 packs can be connected in parallel for expanding capacity and
power with 8 DIP switches.
Working temperature range is from -20
℃
~50
℃
(Charging 0
℃
~50
℃
; discharging -20
℃
~50
℃
)
with excellent discharge performance and cycle life.
2.2 Specifications
Basic Parameters
PUSUNG
Nominal Voltage (V)
51.2V
Nominal Capacity (Ah)
100Ah
Nominal Power (Wh)
5.12KWh
Dimension (mm)
565*440*170mm
Weight (Kg)
56.2KG
Discharge Cut-off Voltage (V)
41.6V
Charge Voltage (V)
54.5V
Max. Charge/Discharge Current (A)
100A
Communication Interface
CAN,RS485
Configuration
16S1P
Working Temperature
0
~
50
℃
(Charge)
-20
~
50
℃
(Discharge)
-20
~
55
℃
(Storage)
Cell chemistry
Lithium iron phosphate (LiFePO4)
Cycle life
≥80% capacity state after 4800
cycles at 0.5C, 25
℃
, 100% DOD
IP level
IP 20