SolaSmart™ Plus Installation Guide
Version 1.1 – Mar 2012
Page 18
B
IO
S
AFE
,
R
EHEAT
,
AND
B
OOST
F
UNCTIONS
Collector
BioSafe
During BioSafe the pump is run for two minutes once the tank is above the
target temperature.
BioSafe Mode
BioSafe runs periodically according to the settings. Only Inlet (Lower Tank)
Sensor is used and Lower Element will be turned on when the controller is in
the BioSafe Mode.
For installations where the Inlet (lower tank) sensor is below the electric
element, BioSafe must use the Tank (upper tank) sensor for control and
should be set to run every 24 hours to comply with AS 3498 Clause 7.1 (j)
BioSafe uses the Real Time Clock to determine when it should run and is
therefore immune to power outages less than 14 days.
BioSafe Target
The controller ensures that the whole tank is above this temperature during
BioSafe Mode.
BioSafe Holdup
The time BioSafe Target Temperature will maintain before exiting BioSafe
Mode. If Lower Tank Temperature drops below BioSafe Target Temperature,
the holdup timer is reset for the full BioSafe Holdup.
BioSafe Band
BioSafe can be specified to run at the start of any of the four Tariff band.
(Refer to “
Tariff Table
” on page 21)
BioSafe Period
It is the interval that BioSafe takes to repeat its operation, nominally every 7
days.
Continued on next page