Indoor Unit 

Installation

Use the holder at the back
of the unit against on the
mounting plate to prop up
the unit

If there is no refrigerant piping embedded in 

the wall, 

do the following:

 

Step 3.

 Connect drain hose and refrigerant 

piping (refer to 

Refrigerant Piping Connection

section of this manual for instructions).

 

Step 4.

 Keep pipe connection point exposed to

perform the leak test (refer to 

Electrical Checks

and Leak Checks 

section of this manual).

 

 

Step 5. 

After the leak test, wrap the connection 

point with insulation tape. 

Step 6. 

Remove the bracket or wedge that is 

propping with insulation tape. 

 

Step 7. 

Using even pressure, push down on the 

bottom half of the unit. Keep pushing down
until the unit snaps onto the hooks along the
bottom of the mounting plate.

1.

Based on the position of the wall hole relative

to the mounting plate, choose the side from

which the piping will exit the unit.

2.

 

If the wall hole is behind the unit, keep the

knock-out panel in place. If the wall hole is to

the side of the indoor unit, remove the plastic

knock-out panel from that side of the unit.

(See figure below). This will create a slot through

which your piping can exit the unit. Use

needle nose pliers if the plastic panel is too

difficult to remove by hand.

3.

 

Use scissors to cut down the length of the

insulating sleeve to reveal about 40mm (1.57in)

of the refrigerant piping. This serves two purposes:

To facilitate the 

Refrigerant Piping

Connection

 process.

To facilitage 

Gas Leak Checks 

and enable

you to check for dents

Knock-out Panel

(cut depending on the 

actual size needed)

If need to cut the big size plastic 

panel, cut as shown above.

2. Use the holder at the back of the unit to

prop up the unit, giving you enough room
to connect the refrigerant piping, signal cable,
and drain hose.

4. Use the holder at the back of the unit to

prop up the unit, giving you enough room
to connect the refrigerant piping, signal cable,
and drain hose.

5.  Connect the indoor unit’s  refrigerant piping

to the connective piping that will join the
indoor and outdoor units. Refer to the

Refrigerant Piping Connection 

section

of this manual for detailed instructions.

6. Based on the position of the wall hole

relative to the mounting plate, determine the

necessary angle of your piping.

7. Grip the refrigerant piping at the base of the bend.
8. Slowly, with even pressure, bend the piping

towards the hole. 

Do not 

dent or damage the

piping during the process.

Page 23 

Содержание SENA/09HF/IQ

Страница 1: ...sure to save this manual for future reference Please check the applicable models technical data F GAS if any and manufacturer information from the Owner s Manual Product Fiche in the packaging of the...

Страница 2: ...Owner s Manual Table of Contents Safety Precautions 04 Care and Maintenance 11 Troubleshooting 13 1 Indoor unit display 07 2 Operating temperature 08 3 Other features 09 4 Setting angle of airflow 10...

Страница 3: ...Unit Installation 28 1 Select installation location 28 2 Install drain joint 29 3 Anchor outdoor unit 29 4 Connect signal and power cables 30 Refrigerant Piping Connection 32 A Note on Pipe Length 32...

Страница 4: ...s rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or paint near the unit Th...

Страница 5: ...exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules For all electrical work follow all local and national wiring standards regulations and th...

Страница 6: ...uxiliary electric heater do not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible ga...

Страница 7: ...ntelligent eye Display Code Meanings Unit Specifications and Features Indoor unit display Unit Specifications and Features for 3 seconds when TIMER OFF is set Displays temperature operation feature an...

Страница 8: ...the following Keep doors and windows closed Limit energy usage by using TIMER ON and TIMER OFF functions Do not block air inlets or outlets Regularly inspect and clean air filters FOR OUTDOOR UNITS WI...

Страница 9: ...Active clean operation is used to produce more condensed water to improve the cleaning effect and the cold air will blow out After cleaning the internal wind wheel then keeps operating with hot air t...

Страница 10: ...r near the blower and suction side of the unit The high speed fan inside the unit may cause injury Fig A Fig B Setting Angle of Air Flow Setting horizontal angle of air flow To operate your unit manua...

Страница 11: ...ular and too much noisy so please clean the air filter as often as necessary Once the abnormal noise of air flow is heard please clean the air filter immediately 1 The air filter is on the top of the...

Страница 12: ...lan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the power Re...

Страница 13: ...hooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may occur after running the un...

Страница 14: ...r service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following points bef...

Страница 15: ...ng performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refri...

Страница 16: ...t Condenser coil temperature sensor T3 open circuit or short circuit Compressor discharge temperature sensor TP open circuit or short circuit Outdoor unit EEPROM parameter error Outdoor fan speed has...

Страница 17: ...er holder Drain joint Seal Mounting plate Manual Accessories 2 3 1 1 1 1 2 1 2 Battery AAA Small Filter 1 2 depending on models Name of Accessories Name of Accessories Qty pc Shape Qty pc Shape Name S...

Страница 18: ...STEP 8 Wrap Piping and Cable not applicable for some locations in North America Connect Piping Prepare Drain Hose Connect Wiring not applicable for some locations in North America 4 5 6 7 8 9 Distance...

Страница 19: ...The actual shape of your indoor unit may be slightly different The actual shape shall prevail Fig 2 1 Drainage Pipe Signal Cable Refrigerant Piping Remote Controller Wall Mounting Plate Front Panel Lo...

Страница 20: ...ctrical devices e g TV radio computer DO NOT install unit in the following locations Near any source of heat steam or combustible gas Near flammable items such as curtains or clothing Near any obstacl...

Страница 21: ...help seal it when you finish the installation process CAUTION When drilling the wall hole make sure to avoid wires plumbing and other sensitive components NOTE When the gas side connective pipe is 16...

Страница 22: ...the wall Refer to the Refrigerant Piping Connection section of this manual for detailed instructions on pipe flaring and flare torque requirements technique etc NOTE ON PIPING ANGLE Refrigerant pipin...

Страница 23: ...a slot through which your piping can exit the unit Use needle nose pliers if the plastic panel is too difficult to remove by hand 3 Use scissors to cut down the length of the insulating sleeve to rev...

Страница 24: ...essor or any moving parts within the unit If the unit has an auxiliary electric heater it must be installed at least 1 meter 40in away from any combustible materials To avoid getting an electric shock...

Страница 25: ...5 Feed the signal wire through this slot from the back of the unit to the front 6 Facing the front of the unit connect the wire according to the indoor unit s wiring diagram connect the u lug and fir...

Страница 26: ...ping drain hose and the signal cable through the wall hole you must bundle them together to save space protect them and insulate them This may not applicable for some locations in US 1 Bundle the drai...

Страница 27: ...g to the outdoor unit do the following 1 If you have already passed the refrigerant piping through the hole in the wall proceed to Step 4 2 Otherwise double check that the ends of the refrigerant pipe...

Страница 28: ...needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or snow Build...

Страница 29: ...in joint to redirect water from the unit during heating mode Seal Drain joint A B Base pan hole of outdoor unit Seal IN COLD CLIMATES In cold climates make sure that the drain hose is as vertical as p...

Страница 30: ...AT ALL TIMES CAUTION Make sure that the wall is made of solid brick concrete or of similarly strong material The wall must be able to support at least four times the weight of the unit Step 4 Connect...

Страница 31: ...the unit in accordance with local codes 6 Be sure to size each wire allowing several inches longer than the required length for wiring 7 Use lock nuts to secure the conduit tubes In North America Cov...

Страница 32: ...ake sure that the pipe is cut at a perfect 90 angle Oblique Rough Warped 90 DO NOT DEFORM PIPE WHILE CUTTING Be extra careful not to damage dent or deform the pipe while cutting This will drastically...

Страница 33: ...ling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve an airtight...

Страница 34: ...of valves 3 Align flared pipe end with each valve and tighten the flare nut as tightly as possible by hand 4 Using a spanner grip the body of the valve Do not grip the nut that seals the service valve...

Страница 35: ...rt Larger Low Pressure Valve Service Port 1 4 to5 16 Adaptor for R134A Coolant Smaller High Pressure Valve Manifold High Pressure Valve 0 0 3 50 100 150 200 250 300 350 0 100 200 300 400 500 500 600 F...

Страница 36: ...all valves and ports and tughten them by hand OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it hits against the stopper Do not try to force the valve to open furthe...

Страница 37: ...thod Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using l...

Страница 38: ...During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that al...

Страница 39: ...Outdoor Unit 1 Cut the packing belt 2 Take the unit out of the carton 3 Remove the foam from the unit 4 Remove the packaging bag from the unit Packing Indoor unit 1 Put the indoor unit into the packi...

Страница 40: ......

Страница 41: ...ations are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website ht...

Отзывы: