INSTALLATION INSTRUCTIONS

      senvainc.com   1-866-660-8864    (F)1-503-296-2529    9290 SW Nimbus Ave.    Beaverton Oregon 97008

AQD Duct Series 

AQO Outdoor Series

Analog and BACnet versions
CO2/RH/T Combination Sensor

IMPORTANT  WARNINGS

•   Only qualified trade installers should install this product
•   This product is not intended for life-safety applications
•   Do not install in hazardous or classified locations
•   The installer is responsible for all applicable codes
•    De-energize power supply prior to installation or service

PRODUCT APPLICATION LIMITATION:

Senva products are not designed for life or safety applications. 

Senva products are not intended for use in critical applications 

such as nuclear facilities, human implantable device or life sup-

PRODUCT IDENTIFICATION

OPERATION 

The AQ series design allows customization for a sensor that 

meets project requirements for monitoring temperature, CO2 

and relative humidity. The product can be ordered for outdoor 

or duct mount and with a 0-5/10V analog or BACnet RS485 

output.  

To verify the features see the ‘Product Identification’ section of 

the installation manual. 

 

RTD/Thermistor*

A = None
C = 100Pt (385) RTD
D = 1000Pt (385) RTD
E = 10k type 2
F = 10k type 3

Output

CO2 Sensor

A = None
B = CO2 Sensor
D = Dual Channel CO2

RH Sensor

A = None
B = 2% RH Sensor

Output Type

A = Analog (0-5/10V)
B = BACnet

CO2

RH

RTD/TH

D

*Add-on RTD/Thermistor is not readable via BACnet.; 
Temperature output is standard on AQ devices.

AQ       -

Package

D = Duct

O = Outdoor

INSTALLATION

AQD (Duct) Installation

1. Drill a 3/4” hole in duct. Install sensor using gasket and 

screws provided. The pickup tube will ensure adequate air flow 

regardless of air flow direction. 
2. Mount unit to duct with supplied screws.  Continue to step 3 

under general installation.

AQO (Outdoor) Installation

1. Select an outdoor location under an eave on north side of 

building away from direct sunlight and rain exposure. 
2. Mount product to building with supplied screws.  Continue 

to step 3 under general installation.

General (both) Installation

3. If installing with a conduit adapter, remove and replace the 

factory-installed cable gland.
4. Wire analog (or RS485 for BACnet version) outputs as needed. 
5. Apply power to sensor.
6. Tighten cable gland firmly around wires. If installing with a 

conduit adapter, seal wire entry to prevent conduit air from 

affecting sensor readings or operation.
7. Close lid and tighten screw. Cover must be securely installed 

to prevent moisture from entering enclosure.

AQD (Duct)

AQO (Outdoor)

G = 10k w/11k
H = 3k
I = 2k2
J = 1k8
K = 20k