M6DXF2
P. / 4
EM-7848 Rev.
INPUT/OUTPUT RANGING
The internal DIP switch setting is required to select input
and output types before setting a precise range using PC
Configurator Software (model: M6CFG).
For detailed information on the PC configuration, refer to
the M6CFG users manual.
Table 1. DIP switch setting: Input type
Input Type
Input 1, SW2-1
Input 2, SW2-2
0 – 50mA
ON
ON
-1000 – +1000mV
OFF
OFF
-10 – +10V
OFF
OFF
Table 2. DIP switch setting: Output type
Output
Type
SW1
1
2
3
4
5
6
7
8
0 – 20mA*
1
ON ON OFF OFF OFF OFF ON OFF
-5 – +5V
OFF OFF ON OFF ON OFF OFF ON
-10 – +10V OFF OFF ON OFF OFF ON OFF ON
*1. For 0 – 1mA range, set switches as in the table below.
Output
Range
SW1
1
2
3
4
5
6
7
8
0 – 1mA
OFF OFF ON OFF OFF OFF ON OFF
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Check DIP switch setting.
3) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
4) Input: Check that the input signal is within 0 – 100% of
the full-scale.
5) Output: Check that the load resistance meets the de-
scribed specifications.
STATUS INDICATOR LED
The transmitter is provided with a status indicator LED
which flashes in different patterns indicating various oper-
ating status.
The following figure indicates typical patterns.
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes.
• For math functions:
Apply the input signals which should lead the calculated
results as 0%, 25%, 50%, 75% and 100%.
• For Hi signal selector functions:
Apply 0%, 25%, 50%, 75% and 100% signal at Input 1
while maintaining 0% at Input 2. Then apply 0%, 25%,
50%, 75% and 100% signal at Input 2 while maintaining
0% at Input 1.
• For Lo signal selector functions:
Apply 0%, 25%, 50%, 75% and 100% signal at Input 1
while maintaining 100% at Input 2. Then apply 0%, 25%,
50%, 75% and 100% signal at Input 2 while maintaining
100% at Input 1.
Check that the output signal for the respective input signal
remains within accuracy described in the data sheet.
When the output is out of tolerance, recalibrate the unit us-
ing the PC Configurator Software (model: M6CFG).
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.
EXTERNAL VIEWS
■
FRONT VIEW (with the cover open)
■
SIDE VIEW
5
6
7
8
1
2
3
4
SW1
Output Range Selectors
Input Range Selectors
Status Indicator LED
Power LED
Configurator Jack
1
2
3
4
5
6
7
8
OFF
ON
SW1
SW2
1
2
OFF
ON
SW2
Normal operating mode
TRANSMITTER STATUS
ON
OFF
LED ON-OFF PATTERNS
Abnormal operating mode