Appendix
A.3 MODBUS
SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
239
A.3.8
Maximum values with a time stamp and the function codes 0x03 and 0x04
Addressing the maximum values with a time stamp
SENTRON PAC4200 provides the maximum values listed below with a time stamp.
Table A- 15 Available measured variables: Maximum values with time stamp
Offset Number of
registers
Name
Format
Unit
Value range
Access
3001
6
Maximum Voltage a-n with Time
Float + time stamp V
-
R
3007
6
Maximum Voltage b-n with Time
Float + time stamp V
-
R
3013
6
Maximum Voltage c-n with Time
Float + time stamp V
-
R
3019
6
Maximum Voltage a-b with Time
Float + time stamp V
-
R
3025
6
Maximum Voltage b-c with Time
Float + time stamp V
-
R
3031
6
Maximum Voltage c-a with Time
Float + time stamp V
-
R
3037
6
Maximum Current a with Time
Float + time stamp A
-
R
3043
6
Maximum Current b with Time
Float + time stamp A
-
R
3049
6
Maximum Current c with Time
Float + time stamp A
-
R
3055
6
Maximum Apparent Power a with
Time
Float + time stamp VA
-
R
3061
6
Maximum Apparent Power b with
Time
Float + time stamp VA
-
R
3067
6
Maximum Apparent Power c with
Time
Float + time stamp VA
-
R
3073
6
Maximum Active Power a with Time
Float + time stamp W
-
R
3079
6
Maximum Active Power b with Time
Float + time stamp W
-
R
3085
6
Maximum Active Power c with Time
Float + time stamp W
-
R
3091
6
Maximum Reactive Power a (VARn)
with Time
Float + time stamp VAR
-
R
3097
6
Maximum Reactive Power b (VARn)
with Time
Float + time stamp VAR
-
R
3103
6
Maximum Reactive Power c (VARn)
with Time
Float + time stamp VAR
-
R
3109
6
Maximum Total Reactive Power a
(VARtot) with Time
Float + time stamp VAR
-
R
3115
6
Maximum Total Reactive Power b
(VARtot) with Time
Float + time stamp VAR
-
R
3121
6
Maximum Total Reactive Power c
(VARtot) with Time
Float + time stamp VAR
-
R
3127
6
Maximum Reactive Power a (VAR1)
with Time
Float + time stamp VAR
-
R
3133
6
Maximum Reactive Power b (VAR1)
with Time
Float + time stamp VAR
-
R
3139
6
Maximum Reactive Power c (VAR1)
with Time
Float + time stamp VAR
-
R
3145
6
Maximum Power Factor a with Time Float + time stamp -
0 … 1
R
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...