Startup
7.6 Check the displayed measured values
SENTRON PAC4200
112
System Manual, 09/2009, A5E02316180B-02
Direction of current flow
Please take account of the direction of current flow when connecting the current measuring
inputs. With inverse connection, the measured values are inverted and receive a negative
sign.
To correct the direction of current flow, it is not necessary to reverse the input terminals.
Instead, change the interpretation of the direction in the device settings.
You can find information about the device settings in the "Basic parameters" section of the
"Parameterization via the user interface" chapter.
See also
Safety instructions (Page 17)
Measuring inputs (Page 24)
Basic parameters (Page 137)
Safety notes (Page 79)
7.6
Check the displayed measured values
Correct connection type
With the help of the table "Displaying the measured variables depending on the connection
type", check whether the measured variables are displayed in accordance with the
connection type executed. Any deviation indicates a wiring fault or configuration error.
See also
Measured variables (Page 25)