Description
3.2 Measuring inputs
SENTRON PAC4200
24
System Manual, 09/2009, A5E02316180B-02
Protection
Password protection by means of a 4-character code.
See also
Measured variables (Page 25)
Technical data (Page 175)
Sliding window demand values (Page 31)
3.2
Measuring inputs
Current measurement
CAUTION
Alternating current measurement only, otherwise the device will become non-functional
Use the device to measure alternating current only.
SENTRON PAC4200 is designed for:
●
Measuring current of 1 A or 5 A for connecting current transformers. Each current
measuring input can take a continuous load of 10 A. Surge withstand capability is
possible for currents up to 100 A and a duration of 1 s.
Voltage measurement
CAUTION
Alternating voltage measurement only, otherwise the device will become non-functional
Use the device to measure alternating voltage only.
SENTRON PAC4200 is designed for:
●
Direct measurement on the system or using voltage transformers. The measuring voltage
inputs of the device measure direct via protective impedances. External voltage
transformers are required to measure higher voltages than the permissible rated input
voltages.
●
Measuring voltage up to 400 V / 690 V (max. 347 V / 600 V for Vph) on devices with a
wide-voltage power supply. The device is designed for measuring input voltages up to
400 V (347 V for Vph) phase-to-neutral and 690 V (600 V for Vph) phase-to-phase.
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...