Figure 6 - Removing Detector Cap

Attach the smoke detector to its mounting base as
follows:

- Line up the raised tab on the lip of the smoke detector
   with slot on the lip of the mounting base. See
   Figure 4.

- Insert the smoke detector into the base and turn
  clockwise approximately 15 degrees.  It should snap
  firmly into place.

WHEN TO REPLACE THE BATTERIES

When the batteries are low, the detector sends a low
battery signal to the control panel, waits several days
and then chirps every 30 seconds until the batteries are
replaced.  The sounder can be silenced for 24 hours by
pushing the Test/Silence button. See 

Specifications for

battery type list.

REPLACING THE BATTERIES

Use only 3V lithium batteries listed in 

Specifications in

the detector.

1. Remove the detector from the mounting base.  See

Attaching and Removing the Detector.

2. Slide the battery compartment cover away from the

detector to unsnap it and lift it off.  See Figure 4.

3. Remove the batteries and dispose of properly.

4. Observing correct polarity, insert two new 3V lithium

batteries into the battery compartment and replace
the cover.

5. Reattach the detector to the mounting base.  See

Attaching and Removing the Detector.

6. Test the system.

CLEANING THE DETECTOR

Clean the detector cover with a dry or damp (water)
cloth as needed to keep it free from dust and dirt.

When necessary, clean the detector interior and
replace the smoke chamber as follows:

1. Disconnect the alarm notification appliances, service

release devices and extinguishing systems.

2. Remove the detector from its mounting base.  See

Attaching and Removing the Detector.

3 Remove the batteries

.  See  Replacing the Batteries.

4. Slide a flat-blade screwdriver in the slot on the

detector cap and gently push the handle down to pry
the cap up and off.  See Figure 6.

5. Press in on the sides of the smoke chamber and pull

it up and away from the detector and discard.  See
Figure 7.

6. Blow out or use a soft-bristled brush to remove dust

and dirt from the smoke chamber base.

7. Line the new smoke chamber up with the smoke

chamber base and snap down into place.

8. Replace the detector cap as follows:

-Line the cap up with the smoke detector.

-Insert the cap into the smoke detector and turn
 clockwise approximately 15 degrees.  It should
 snap firmly into place.

9. Observing the proper polarity, put the batteries back

in the detector and replace the battery compartment
cover.

10.Reattach the detector to its mounting base.  See

Attaching and Removing the Detector.

11.Test the detector sensitivity (See

Testing the Detector

 Sensitivity)  and reconnect all alarm notification
 appliances, service release devices and extinguish-
 ing systems.

Important: The control panel alarm and all auxiliary
functions should be verified for a complete test of the
system.

Smoke
chamber

SQ

UE

EZ

E

HE

RE

Detector

Optical base

Smoke

Indentation

Figure 7 - Detector Parts

Содержание 4300 Series

Страница 1: ...ED SIGNAL OUTPUTS Depending on the model the detector transmits the following signals to the control panel Alarm Alarm restore Tamper Low battery SELECTING A LOCATION Selecting a suitable location is critical to the operation of smoke detectors This equipment should be installed in accordance with the National Fire Protection Association s NFPA Standard 72 See Figure 2 A 8 1 2 1 C Are More Smoke D...

Страница 2: ...See the control panel programming guide 6 Remove the red plastic dust cover from the detector The detector is shipped with a dust cover for protec tion on construction sites with dusty environments 7 Disconnect the alarm notification appliances service release devices and extinguishing systems and test the communication between the control panel and each smoke detector before permanently mounting ...

Страница 3: ... of the mounting base To remove the detector from the mounting base when the detector base lock is used insert a small screwdriver into the locking tab slot on the side of the base and press in while simultaneously turning the detector counterclockwise 15 degrees See Figure 5 TESTING THE DETECTOR SENSITIVITY The 4300 Series provides a sensitivity level test mode that allows you to check the detect...

Страница 4: ...en necessary clean the detector interior and replace the smoke chamber as follows 1 Disconnect the alarm notification appliances service release devices and extinguishing systems 2 Remove the detector from its mounting base See Attaching and Removing the Detector 3 Remove the batteries See Replacing the Batteries 4 Slide a flat blade screwdriver in the slot on the detector cap and gently push the ...

Страница 5: ...st that everyone meet there during an alarm This will eliminate the tragedy of someone reenter ing the house for a missing member who is actually safe If you have children and or physically challenged people residing in your household use window decals to help emergency personnel identify the sleeping quarters of these individuals LIMITED WARRANTY Sentrol is a brand name of SLC Technologies Inc Th...

Страница 6: ...moke detectors are very reliable but may not work under all conditions No fire detector provides total protection of life or property Smoke detectors are not a substitute for life insurance Smoke detectors require a source of power to work This smoke detector will not operate and the alarm will not sound if batteries are dead or not installed properly Unreliable transmission or receiving of radio ...

Страница 7: ...7 ...

Страница 8: ...ncoded Signal types Primary address alarm restore tamper low battery trouble maint CleanMe 1 hour supervisory Secondary address L models alarm restore Listings 4310 Series UL 217 CSFM 4330 Series UL 268 CSFM Approvals FCC IC l e d o M n o i t p i r c s e D S 0 1 3 4 d e t s i L 7 1 2 L U r e d n u o s B d 5 8 s e i r e t t a b m u i h t i l V 3 o w t r o t c e t e d e k o m s s s e l e r i w l o r...

Отзывы: