![Sentrol 4300 Series Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/sentrol/4300-series/4300-series_user-manual_1244813004.webp)
4
Figure 6 - Removing Detector Cap
Attach the smoke detector to its mounting base as
follows:
- Line up the raised tab on the lip of the smoke detector
with slot on the lip of the mounting base. See
Figure 4.
- Insert the smoke detector into the base and turn
clockwise approximately 15 degrees. It should snap
firmly into place.
WHEN TO REPLACE THE BATTERIES
When the batteries are low, the detector sends a low
battery signal to the control panel, waits several days
and then chirps every 30 seconds until the batteries are
replaced. The sounder can be silenced for 24 hours by
pushing the Test/Silence button. See
Specifications for
battery type list.
REPLACING THE BATTERIES
Use only 3V lithium batteries listed in
Specifications in
the detector.
1. Remove the detector from the mounting base. See
Attaching and Removing the Detector.
2. Slide the battery compartment cover away from the
detector to unsnap it and lift it off. See Figure 4.
3. Remove the batteries and dispose of properly.
4. Observing correct polarity, insert two new 3V lithium
batteries into the battery compartment and replace
the cover.
5. Reattach the detector to the mounting base. See
Attaching and Removing the Detector.
6. Test the system.
CLEANING THE DETECTOR
Clean the detector cover with a dry or damp (water)
cloth as needed to keep it free from dust and dirt.
When necessary, clean the detector interior and
replace the smoke chamber as follows:
1. Disconnect the alarm notification appliances, service
release devices and extinguishing systems.
2. Remove the detector from its mounting base. See
Attaching and Removing the Detector.
3 Remove the batteries
. See Replacing the Batteries.
4. Slide a flat-blade screwdriver in the slot on the
detector cap and gently push the handle down to pry
the cap up and off. See Figure 6.
5. Press in on the sides of the smoke chamber and pull
it up and away from the detector and discard. See
Figure 7.
6. Blow out or use a soft-bristled brush to remove dust
and dirt from the smoke chamber base.
7. Line the new smoke chamber up with the smoke
chamber base and snap down into place.
8. Replace the detector cap as follows:
-Line the cap up with the smoke detector.
-Insert the cap into the smoke detector and turn
clockwise approximately 15 degrees. It should
snap firmly into place.
9. Observing the proper polarity, put the batteries back
in the detector and replace the battery compartment
cover.
10.Reattach the detector to its mounting base. See
Attaching and Removing the Detector.
11.Test the detector sensitivity (See
Testing the Detector
Sensitivity) and reconnect all alarm notification
appliances, service release devices and extinguish-
ing systems.
Important: The control panel alarm and all auxiliary
functions should be verified for a complete test of the
system.
Smoke
chamber
SQ
UE
EZ
E
HE
RE
Detector
Optical base
Smoke
Indentation
Figure 7 - Detector Parts