Mounting and operating instructions

RSCOX-R

MULTIFUNCTIONAL 
ROOM TRANSMITTER

 

Содержание RSCOF-G

Страница 1: ...Mounting and operating instructions RSCOX R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Страница 2: ...ODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING OPERATING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 9 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 RSCOX R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Страница 3: ...environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connect...

Страница 4: ...VDC mode min load 50 kΩ RL 50 kΩ 0 20 mA mode max load 500 Ω RL 500 Ω PWM mode open collector type PWM Frequency 1 kHz min load 50 kΩ RL 50 kΩ PWM voltage level 3 3 or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 0 100 Selectable CO range 0 1 000 ppm Replaceable CO NO2 sensor element Warm up time 1 hour 3 LEDs with adjustable light intensity for status indication A...

Страница 5: ...nditioning Low Voltage Directive 2014 35 EU EN 60529 1991 Degrees of protection provided by enclosures IP Code Amendment AC 1993 to EN 60529 EN 60730 1 2011 Automatic electrical controls for household and similar use Part 1 General requirements WEEE 2012 19 EC RoHs Directive 2011 65 EC OPERATIONAL DIAGRAMS 10 0 20 30 40 50 60 70 80 90 100 Minimum range Minimum alert Maximum alert Analogue modulati...

Страница 6: ...Minimum 4 wires are required to connect F type sensors The G version is intended for 3 wire connection and features a common ground This means that the ground of the analogue output is internally connected with the ground of the power supply For this reason G and F types cannot be used together on the same network Never connect the common ground of G type articles to other devices powered by a DC ...

Страница 7: ... see Fig 4 Fig 4 Wiring and connections Supply voltage RSCOF R 18 34 VDC RSCOG R 18 34 VDC 15 24 VAC 10 Modbus RTU A B Analogue modulating output 1 temperature Analogue modulating output 2 relative humidity Analogue modulating output 3 CO NO2 5 Put back the cover snap it in 6 Switch on the mains supply 7 Customise the factory settings to the desired ones via the 3SModbus software or Sensistant if ...

Страница 8: ...UCTIONS The warm up time for the sensor to attain its highest accuracy and performance level once the voltage supply has been applied is 1 hour During warm up time CO and NO2 measurement will return 0 ppm NOTE Calibration procedure Sensor calibration is not necessary All sensor elements are calibrated and tested in our factory In the unlikely event of CO NO2 sensor element failure this component c...

Страница 9: ... level Input Register 42 indicates Active Standby level Ambient light level Active level Input Register 42 indicates Low intensity VERIFICATION OF INSTALLATION INSTRUCTIONS After switching on the power supply one of the LEDs lights up according to the status of the measured variable If this is not the case check the connections TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in ori...