www.sentera.eu
MIW-FCVC8-R-EN-000 - 28 / 08 / 2019
5 - 12
Part 1: General requirements
■
EMC Directive 2014/30/EC;
►
EN 60730-1:2011 Automatic electrical controls for household and similar use -
Part 1: General requirements
►
EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic
standards - Immunity for residential, commercial and light industrial environments
EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic
standards - Emission standard for residential, commercial and light-industrial
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3
►
EN 61326-1:2013 Electrical equipment for measurement, control and laboratory
use - EMC requirements - Part 1: General requirements
►
EN 61326-2-3:2013 Electrical equipment for measurement, control and
laboratory use - EMC requirements - Part 2-3: Particular requirements - Test
configuration, operational conditions and performance criteria
■
WEEE 2012/19/EC
■
RoHs Directive 2011/65/EC
OPERATIONAL DIAGRAMS
AO1, max
range
AO1, min
range
60
40
100
0
rH Min range
-30
0
0 TVOC Min range
TVOC Max range
Max
Min
T Min
range
T Max
range
rH Max range
AO1 [%]
70
100
60.000
rH [%]
T [°C]
TVOC [ppb]
CAUTION
The output changes automatically depending on the highest T, rH or TVOC values,
i.e. the highest of the three output values controls the output. See the green line in
the operational diagram above.
NOTE
The replaceable sensor element measures TVOC. Based on this TVOC value, a
CO
2
equivalent is calculated. However, CO
2
eq value cannot be used to control the
output.
WIRING AND CONNECTIONS
L
Power supply, line (85—264 VAC / 50—60 Hz)
N
Power supply, neutral
Ao
Analogue / modulating output - T, rH or TVOC
(0—10 VDC / 0—20 mA / PWM)
GND
Ground AO
A
Modbus RTU (RS485), signal A
/B
Modbus RTU (RS485), signal /B
Connections
Spring contact terminal block, cable cross section: 2,5 mm
2
;
pitch 5 mm; shielded cable
FCVC8-R
INTELLIGENT MULTIFUNCTIONAL