STVS1

230 VAC TRANSFORMER CONTROLLER WITH
ANALOGUE INPUT

MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the STVS1, read carefully 

Safety and Precautions”

 and 

follow these steps. Choose a smooth solid surface for installation (a wall, panel, 
etc.).

Follow these steps:

1. 

 Unscrew the front cover and open the enclosure. Mind the wires that connect the 
front cover with the printed circuit board. 

2. 

 Fix the unit onto the wall or panel using the provided screws and dowels. Mind the 
correct mounting position and unit mounting dimensions. (See

 Fig. 1

 

Mounting 

dimensions

 and 

Fig. 2

 

Mounting position

.)

3. 

 Pay attention to the following instructions in order to minimize the operating 
temperature:

3.1 

 Respect the distances both between the wall / ceiling and the device and 
between  two devices as shown in 

Fig. 2. 

In order to ensure sufficient 

ventilation of the controller, clearance on every side has to be maintained.

3.2 

 When installing the device, please keep in mind that the higher you install  
it, the warmer the device will get. For example, in a technical room the 
correct installation height can be of great importance. 

3.3 

 If maximum ambient temperature cannot be adhered to, please provide 
extra forced ventilation / cooling. 

Not respecting the abovelisted rules can reduce service life and relieves the 

manufacturer of any responsibilities. 

For metal enclosures (above 7.5 A)

4. 

 Once secured in position, the mounting screws or bolts should be sealed to 
maintain the IP rating of the enclosure.

5. 

Because the controller enclosure is made of metal, it must be earthed and bonded

Fig. 1 Mounting dimensions 

Fig. 2 Mounting position

A

C

B

A

C

B

E

D

Article code

A

[mm]

B

[mm]

C

[mm]

D

[mm]

E

[mm]

STVS1-15L22

200

305

140

183

236

STVS1-25L22

200

305

140

183

236

STVS1-35L22

200

305

140

183

236

STVS1-50L22

200

305

140

183

236

STVS1-75L22

200

305

140

183

236

STVS1100L22

300

325

170

255

255

STVS1130L22

300

325

170

255

255

Correct

Incorrect

  50 mm

  50 mm

  75 mm

  50 mm

Wall

6. 

 Insert the cables through the cable glands and do the wiring according to the 
wiring diagram (see 

Fig. 3

) while adhering to the information from section 

Wiring and connections

” above. 

6.1 

Connect the power supply line (terminals L, N and Pe);

6.2 

Connect the motor(s) (terminals U, N and Pe);

6.3 

Connect the 0-10 Volt control signal input (terminals 0V and V/C).

Содержание STVS1 Series

Страница 1: ...STVS1 230 VAC TRANSFORMER CONTROLLER WITH ANALOGUE INPUT Mounting and operating instructions ...

Страница 2: ...ALOGUE INPUT Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 VERIFICATION OF INSTALLATION 8 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 ...

Страница 3: ...fect the product performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts A...

Страница 4: ...STVS1 50L22 5 0 5 20 mm T 8 0 A H STVS1 75L22 7 5 6 32 mm T 12 5 A H STVS1100L22 10 0 6 32 mm T 16 0 A H STVS1130L22 13 0 6 32 mm T 20 0 A H INTENDED AREA OF USE Fan speed control of voltage controllable motors pumps and fans in ventilation systems For indoor use only TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current Imax 13 A Unregulated output 230 VAC Imax 2 A TK monitoring fo...

Страница 5: ...NS Wiring and connections L Power supply phase 230 VAC 50 60 Hz N Power supply neutral Pe Earth terminal Pe Earth terminal L1 Unregulated output line N1 Unregulated output neutral N1 Regulated output to motor neutral U Regulated output to motor line TK Input TK monitoring for thermal motor protection TK 0V Ground 12V Output 12 VDC Imax 50 mA V Digital output 12 VDC Imax 50 mA 0 VDC TK fault 12 VDC...

Страница 6: ...vice will get For example in a technical room the correct installation height can be of great importance 3 3 If maximum ambient temperature cannot be adhered to please provide extra forced ventilation cooling Not respecting the abovelisted rules can reduce service life and relieves the manufacturer of any responsibilities For metal enclosures above 7 5 A 4 Once secured in position the mounting scr...

Страница 7: ...P P P P P P P P P P P P P P P P P P P P P P P X1 X1 X1 X1 X1 X1 X1 X1 X1 1 1 1 1 X1 X1 1 X1 1 1 1 X1 1 1 1 1 1 1 X X X X X X X1 1 X1 X X X X1 X1 1 X1 X1 X1 X1 X1 1 1 X10 0K 0 0 0K 0K 0 0K 0K 0 0 0K K K K K K K K K K K K K 0K K 0K 0K 0 0 0 0K K K K K K K K K K 0K K K 0K 0K 0 0 0 0 0K K K K K K K K K 0K 0 0 0 0 0 0 0K K K K K K K K K 0 0 0 0 0 0 0K K K K K K 0K K K K 0K 0 0 0 0 0 0 0 0 0K K K K 0K 0...

Страница 8: ...ON ATTENTION Use only tools and equipment with non conducting handles when working on electrical devices After connecting the unit to the mains supply the green LED on its cover should light up to indicate that the controller is supplied Safe operation depends on proper installation Before start up ensure the following The mains supply is connected correctly Protection is provided against electric...

Страница 9: ...alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should b...

Отзывы: