VERIFICATION OF INSTALLATION INSTRUCTIONS
When you switch on the unit the green LED (
Fig 8
Power indication
) should give out
continuous green light. If it does, your unit is powered on. If this is not the case,
check the connections again.
Fig. 8 Power indication
NOTE
Rapid, continuous blinking of the blue LED (
Fig. 10
Sensor calibration / Modbus
register reset / normal operation indication) indicates that the unit operates properly.
Check if the LEDs shown in
Fig. 9
Modbus communication indication
blink. If they do,
your unit has detected a Modbus network. If they do not blink, check the connections
again.
Fig. 9 Modbus communication indication
ATTENTION
The status of the LEDs can be checked only when the unit is energised. Take the
relevant safety measures!
OPERATING INSTRUCTIONS
1.
Calibration procedure:
ATTENTION
Make sure that the nozzles are free and not connected.
1.1
Disconnect the nozzles.
1.2
Press button SW2 (
Fig. 10
) for 4 seconds until the blue LED on the printed
circuit board blinks twice. (See
Fig. 11
Sensor calibration and Modbus
register reset indication
.) Then release this button.
1.3
In 2 seconds the blue LED blinks twice to show that the calibration
procedure has finished.
SPS
DIFFERENTIAL PRESSURE
TRANSMITTER