www.sentera.eu
MIW-SDX-Y-EN-000 - 31 / 03 / 2022
6 - 8
SD
ELECTRONIC FAN SPEED
CONTROLLER
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting the unit, read carefully
“Safety and Precautions”
and
follow the steps:
Flush mounting
1.
Disconnect the mains supply.
2.
Remove the knob by pulling it out.
3.
Unscrew the washer to remove the cover of the external enclosure.
4.
Do the wiring according to the wiring diagram (see
Fig. 1
Wiring and connections
).
5.
Mount the internal enclosure into the wall according to the mounting dimensions
shown in
Fig. 2
Mounting dimensions - flush mounting.
Fig. 1 Wiring and connections
Power Supply:
230 VAC / 50—60 HZ
Unregulated output:
230 VAC ±10 % / 50—60 Hz, Imax 2 A
Regulated output to
motor
Minimum speed
adjustment trimmer
(factory pre set to
100 VAC)
Fig. 2 Mounting dimensions - flush mounting
58
58
58
58
4x ø 3,5m
m
4x ø 3,5m
m
58
58
76
76
Correct
Incorrect
NOTE
Mount the unit so that the terminal block and connections are at the lower side.