www.sentera.eu
MIW-HPS-X-2-EN-000 - 14 / 03 / 2017
4 - 15
PRODUCT DESCRIPTION
The HPS-X -2 series are high resolution differential pressure transmitters with
Modbus RTU communication, which are equipped with a fully digital pressure
transducer designed for a wide range of applications. Air flow velocity readout is
available by connecting an external Pitot tube connection set. All parameters are
accessible via Modbus RTU (3S Modbus software or Sensistant).
ARTICLE CODES
Article code
Power supply
Connection
Range, [Pa]
HPS-F-1K0-2
18—34 VDC
4-wire (separate grounds)
0—1.000 Pa
0—2.000 Pa
0—4.000 Pa
0—10.000 Pa
HPS-F-2K0-2
HPS-F-4K0-2
HPS-F-10K -2
HPS-G-1K0-2
18—34 VDC /
15—24 VAC ± 10 %
3-wire
*
(common ground)
0—1.000 Pa
0—2.000 Pa
0—4.000 Pa
0—10.000 Pa
HPS-G-2K0-2
HPS-G-4K0-2
HPS-G-10K -2
INTENDED AREA OF USE
■
Differential pressure measurement in HVAC applications
■
Air flow volume measurement ** in HVAC applications
■
Air flow velocity measurement (by using an external PSET-PTX-200 Pitot tube
connection set) in HVAC applications
■
Differential pressure / airflow monitoring in clean rooms
■
Clean air and non-aggressive, non-combustible gases
TECHNICAL DATA
■
Built-in digital high resolution differential pressure sensor
■
Air flow velocity can be measured via Modbus RTU (by using an external PSET-
PTX-200 Pitot tube connection set)
■
Selectable analogue / digital output: 0—10 VDC / 0—20 mA / PWM (open collector
type):
►
0—10 VDC mode: min. load 50 kΩ (RL ≥ 50 kΩ)
►
0—20 mA mode: max. load 500 Ω (RL ≤ 500 Ω)
►
PWM mode: PWM Frequency: 1 kHz, min. load 50 kΩ (RL ≥ 50 kΩ)
■
Variety of operating ranges and measurement windows
■
Minimum differential pressure range span: 50 Pa
■
Minimum volume flow range span: 10 m
3
/h
■
Minimum air velocity range span:1 m/s
■
Selectable response time: 0,1—10 s
■
Implemented K-factor
■
Selectable internal voltage source for PWM output – 3,3 or 12 VDC
■
Differential pressure, air volume** or air velocity readout via Modbus RTU
■
Selectable minimum and maximum operating ranges
■
Modbus registers reset function (to factory pre-set values)
■
Four LEDs with light guides for transmitter status indication
* In case of 3-wire connection, the analogue output GND signal is internally connected with the GND of the power supply. Therefore, G and F-type devices
cannot be used together in the same network. G and F-type devices must be supplied with separate power supplies. Do not connect the GND terminals of G
and F-type devices together!
*
*
Only when K-factor of fan / drive is known. If K-factor is unknown, air volume flow can be calculated via multiplying the duct cross-sectional area (A) by the
air flow velocity (V) using the formula: Q = A * V
DIFFERENTIAL PRESSURE
TRANSMITTER
HPS-X -2