www.sentera.eu
MIW-FCMFX-R-EN-000 - 29 / 05 / 2021
6 - 10
FCMFX-R
INTELLIGENT CO
2
SENSOR
*
LED indications - T, rH or CO
2
(default)
WIRING AND CONNECTIONS
Article type
FCMFF-R
FCMFG-R
V+
18—34 VDC
18—34 VDC
15—24 VAC ±10%
V-
Ground
Common
ground
AC ~
A
Modbus RTU (RS485), signal A
/B
Modbus RTU (RS485), signal /B
AO
Analogue / modulating output
(0—10 VDC / 0—20 mA / PWM)
GND
Ground AO
Common ground
Connections
Spring contact terminal block, cable cross section: 2,5 mm
2
; pitch 5
mm; shielded cable
ATTENTION
The -F version of the product is not suited for 3-wire connection. It has separate
grounds for power supply and analogue output. Connecting both grounds together
might result in incorrect measurements. Minimum 4 wires are required to connect
-F type sensors.
The -G version is intended for 3-wire connection and features a ‘common ground’.
This means that the ground of the analogue output is internally connected with
the ground of the power supply. For this reason, -G and -F types cannot be used
together on the same network. Never connect the common ground of -G type
articles to other devices powered by a DC voltage. Doing so might cause permanent
damage to the connected devices.
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting the unit, read carefully
“Safety and Precautions”
.
Choose a smooth surface for installation (a wall, panel, etc.). Then proceed with
the following steps:
ATTENTION
When planning the installation, allow enough clearance for maintenance and
service. Mount the sensor in a well-ventilated area.
Inset mounting
1.
Disconnect the supply voltage.
2.
Remove the cover of the enclosure and take the controller out of the housing, so