ATTENTION

Do not exceed the maximum power supply rating! Measure before installation! 
Unregulated 24 VAC supply units provide higher nominal output voltage and 
activate the integrated fuse protection.

ATTENTION

If a G‑type article is using the same AC power supply source (transformer) as 
F‑type article, a SHORT CIRCUIT may result when the power supply and analogue 
signal terminals are connected to the same common ground! In this case always 
connect different article types to separate AC transformers or use the same 
article version.

8. 

 Customise the other factory settings to the desired ones, through 3SModbus 
software  (if necessary). For the default factory setting see 

Table 

Modbus 

register maps

.

MODBUS REGISTER MAPS

INPUT REGISTERS

Data type

Description

Data

Values

1

Temperature level

signed int.

Actual temperature level

 

500 = 

50,0 °C

2

Relative humidity level

unsigned int.

Actual relative humidity level

 

1.000 = 

100,0 % rH

3

Dew point

signed int.

Calculated dew point

 

200 = 

20,0 °C

4-10

 

 

Reserved, returns 0

 

11

Analogue output value

signed int.

Value of the analogue output

0—1.000

0 = 

1.000 = 

0 %

100 %

12

Relay status

signed int.

Relay status.

 When it is On, the contact between COM1 and NO1 is closed.

0—1

0 = 
1 = 

Off

On

13

Relative humidity range

signed int.

Relative humidity working range selected by a jumper or a holding register

1—5

1 = 
2 = 
3 = 
4 =
5 = 

20—90 % rH

0—60 % rH
0—80 % rH

0—100 % rH

Custom

14

Setpoint

signed int.

Setpoint selected by a trimmer or a holding register

0—1.000

500 = 

50,0 % rH

15

Hysteresis

signed int. 

Hysteresis for relative humidity relay switching

1—5

1  =  
2 =
3 =
4 = 
5 =

1,0 % rH

3,0 % rH
5,0 % rH

7,0 % rH

10,0 % rH

16

Setpoint out of range

signed int. 

Flag that shows if the relative humidity setpoint is out of the working range

0—1

0 = 
1 = 

No

Yes

17-19

 

 

Reserved, returns 0

 

20

Humidity sensor 
communication lost

unsigned int.

Flag that shows if the communication with humidity sensor module is lost

0—1

0 = 
1 = 

No

Yes

DXH

  

DUCT HUMIDITY 
SENSOR / SWITCH

Содержание DXH-F

Страница 1: ...Mounting and operating instructions DXH DUCT HUMIDITY SENSOR SWITCH ...

Страница 2: ...NTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 5 MODBUS REGISTER MAPS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 9 TRANSPORT AND STOCK KEEPING INFORMATION 10 WARRANTY INFORMATION AND RESTRICTIONS 10 MAINTENANCE 10 DXH DUCT HUMIDITY SENSOR SWITCH ...

Страница 3: ... as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts always treat the product as if it is live Always disconnect the power ...

Страница 4: ...20 mA Relay output C O 230 VAC 2 A Power consumption no load max 55 mA full load max 75 mA Load resistance 0 10 VDC mode 500 Ω 0 20 mA mode 500 Ω Selectable sensor ranges by trimmer 20 90 rH 0 60 rH 0 80 rH 0 95 rH Free selectable sensor range via Modbus 0 95 rH Selectable switching point by trimmer or via Modbus Hysteresis fixed Standalone mode 5 rH selectable Modbus mode 1 3 5 7 10 rH Accuracy 3...

Страница 5: ...act Connections Cable cross section max 1 5 mm2 Cable gland clamping range 5 10 mm MOUNTING INSTRUCTIONS IN STEPS Before you start mounting the DXH sensor switch read carefully Safety and Precautions Then proceed with the following mounting steps 1 Open the cover and insert the connecting cables through the cable gland of the unit 2 Do the wiring according to the wiring diagram see Fig 1 using the...

Страница 6: ... 20 90 rH 5 4 3 2 1 0 60 rH 5 4 3 2 1 0 80 rH 5 4 3 2 1 0 95 rH 0 20 mA 0 10 VDC 5 4 3 2 1 Put and hold for 20 seconds 4 Check if your unit starts or terminates the network see Example 1 and Example 2 If it does put the NBT JP6 jumper onto the pins If it does not leave the jumper open See Fig 6 Network bus resistor jumper Example 1 Example 2 Fig 6 Network bus resistor jumper Slave 1 RX ТX NBT NBT ...

Страница 7: ... inside the flexible flange Mind the airflow direction 5 3 Install the tube at the desired depth in the duct using the screw in the flexible flange 5 4 Install and connect the cables with a drip loop You can also fix the unit outside the duct via the mounting holes and as per the drawing shown in Fig 7 Fig 9 Fixing flange 2x Ø 5 60 ATTENTION Installation of the unit near high EMI emitting devices ...

Страница 8: ...evel 500 50 0 C 2 Relative humidity level unsigned int Actual relative humidity level 1 000 100 0 rH 3 Dew point signed int Calculated dew point 200 20 0 C 4 10 Reserved returns 0 11 Analogue output value signed int Value of the analogue output 0 1 000 0 1 000 0 100 12 Relay status signed int Relay status When it is On the contact between COM1 and NO1 is closed 0 1 0 1 Off On 13 Relative humidity ...

Страница 9: ...settable Active only if holding register 7 is set to 1 and register 11 is set to 5 0 Max 0 200 20 0 rH 13 Maximum custom relative humidity range signed int Maximum value of the custom relative humidity range Always settable Active only if holding register 7 is set to 1 and register 11 is set to 5 Min 1 000 1 000 1 000 100 0 rH 14 Setpoint signed int Selected setpoint for relay switching Always set...

Страница 10: ...r the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or dampish cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be disconnected from the supp...

Отзывы: