VERIFICATION OF INSTALLATION
ATTENTION
Use only tools and equipment with non-conducting handles when working on
electrical devices.
After switching on the power supply the red LED should be on to indicate that the unit
is supplied. The green LED indicates that the output is active. If this is not the case,
check the connections.
MODBUS REGISTER MAPS
INPUT REGISTERS
Data type
Description
Data
Values
1
Reserved, returns “0”
2
Current output duty cycle
unsigned int.
Current output in %
0—100
100 =
100 %
3—12
Reserved, return “0”
13
Remote Off contact
unsigned int.
Shows if the unit is in remote off,
selected via the NC switch
0, 1
0 =
1=
On
Standby
14
Reserved, returns “0”
15
Control board problem
unsigned int.
Shows if there is a problem with the
communication with the control board
0, 1
0 =
1=
OK
Problem
16—18
Reserved, return “0”
HOLDING REGISTERS
Data type
Description
Data
Default
Values
1
Device slave address
unsigned int.
Modbus device address
1—247
1
2
Modbus baud rate
unsigned int.
Modbus communication baud rate
1—4
2
1 =
2 =
3 =
4 =
9.600
19.200
38.400
57.600
3
Modbus parity mode
unsigned int.
Parity check mode
0 =
1 =
2 =
8N1
8E1
8O1
1
0 =
1 =
2 =
None
Even
Odd
4
Device type
unsigned int.
Device type (Read-only)
AH2A1-6 =
6.003
5
HW version
unsigned int.
Hardware version of the device (Read-only)
XXXX
0 x 0100 =
HW version 1.10
6
RW version
unsigned int.
Firmware version of the device (Read-only)
XXXX
0 x 0110 =
FW version 1.10
7
Operating mode
unsigned int.
Enables / disables the Modbus control
0-1
0 =
1=
Standalone mode
Modbsu mode
8
Output override
unsigned int.
Enables Modbus control over the output.
Always settable. Active only if holding
register 7 is set to 1
.
0, 1
0 =
1=
Disabled
Enabled
9—14
Reserved, return “0”
15
Triac Control PWM Output
Period
unsigned int.
PWM period time
1—60
30
60 =
60 sec
16—20
Reserved, return “0”
21
Override Output Value
unsigned int.
Override output value in %(only active if
registers 7 and 8 are set)
0—100
0
100 =
100 %
22—30
Reserved, return “0”
For more information about Modbus over serial line, please visit:
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
INPUT REGISTERS
The input registers are read-only. All data can be read using the “Read Input Registers”
command.
Table
Input registers
shows the returned data type and the way it should
be interpreted.
HOLDING REGISTERS
These registers are read / write registers and they can be managed via “Read Holding
Registers”, “Write Single Register” and “Write Multiple Registers” commands. The
registers that are not used are read-only and, therefore, writing in these registers
neither returns a Modbus error exception, nor makes any changes.
AH2A1-6
ELECTRONIC HEATING
CONTROLLER