Sensus 441-S Скачать руководство пользователя страница 2

2

Installation and Maintenance Instructions

Model 441-S Regulator

Maximum

Working

Maximum

Regulator

441 Body

Pressure

Inlet

Body Type

Materials

of Body

Pressure

Cast Iron

Screwed End

(ASTM A126-71

250 psi

(2" Pipe Size Only)

Class B)

Cast Iron

Flanged 

(ASTM A126-71

175 psi

ANSI 125 FF

Class B)

100 psi

Ductile Iron

Flanged 

(ASTM A395-71 

575 psi

ANSI 250 RF

gr 60-40-18)

Cast Steel

Flanged 

(ASTM A126-70a

720 psi

ANSI 300 RF

gr WCB)

Installation and Start-Up

1

Thoroughly purge inlet piping to remove dirt and debris which
could damage the regulator or impair its operation. If this 
cannot be done, a filter or strainer should be installed ahead 
of the regulator.

Make certain that regulator is free of any dirt or foreign matter 
that might have collected.

2

Place regulator in the line with high pressure connected to the 
inlet side (be sure that shipping screens or covers, if used, 
are removed from the inlet and outlet).

Tighten bolts on flanges evenly. 

Where required, the regulator may be inverted.

CAUTION

It is the user's responsibility to assure that all regulator vents 
and/or vent lines exhaust to a non-hazardous location away from
ANY POTENTIAL sources of ignition. Where vent lines are used,
it is the user's responsibility to assure that each regulator is
individually vented and that common vent lines ARE NOT used.

3

From the 1/2" union 

60

extend pipe or tubing to the control 

connection into the outlet piping. This control piping should 
not be less than 1/2" in size and should be adequately 
protected against breakage (regulators go wide open if the 
control line is broken). 

The regulator will work to deliver the pressure, for which it is 
adjusted, at that point in the outlet piping where the control 
connection is located.
In general, the control connection should be at least 8 pipe
diameters from the regulator and should be in as straight a 
run of pipe as possible.
The control connection should be clean and smooth, 
free of rough edges, welding “icicles”. etc.

4

Where outlet piping increases in size near the regulator, 
it is generally preferable to locate the control connection in 
the larger size. 

The 1/2" union 

60

contains a small orifice, approximately 

1/16" diameter. This orifice should not be removed. Also, 
make certain this orifice is open and free of foreign material. 

Check all connections for leaks.

CAUTION

Turn gas on very slowly. If an outlet stop valve is used, 
it should be opened first. Do not overload the diaphragm with a
sudden surge of inlet pressure. Monitor the outlet pressure 
during start-up to prevent an outlet pressure overload

.

5

Put the regulator into operation as follows: (refer to page 8)

a.

Slowly open the downstream control line valve (A).

b.

Slowly open the downstream block valve (B).

c.

Very slowly open the upstream block valve (C).

d.

Set the adjusting screw 

10

for the required outlet pressure. 

Turn it clockwise to increase the pressure counterclockwise 
to decrease it. Only make this adjustment when gas 
is actually flowing through the regulator. 

e.

After adjustment is complete, the locknut 

11

should be 

tightened firmly and the seal cap 

1

replaced.

6

To shut down, carefully close valves 

C

B

, and 

A

in that order.

CAUTION

The diaphragm case vent must be positioned to protect against 
flooding, drain water, ice formation, traffic, tampering, etc. The
vent must be protected against nest building animals, bees,
insects, etc. to prevent vent blockage and minimize the chances
for foreign material from collecting in the vent side of the 
regulator diaphragm.

7

The vent connection is an escape path for flammable gas 
and it must be located and/or piped so that potential 
discharge occurs in a safe area away from buildings, 
open flames, collection areas, arcing devices, etc.

Regulators that are installed indoors or in a non-vented
area must be vented to the outside. Simply run vent piping 
from the regulator vent connection to a non-hazardous 
location on the outside away from ANY POTENTIAL sources 
of ignition. The vent piping must be connection size 
or larger and piped to a safe area. The vent discharge 
must be protected against the potentials outlined 
in instructions #2 and #10.

8

For outdoor installations, it is recommended that the 
regulator be installed so that the regulator vent faces 
downward to avoid the potential for water or other foreign 
matter entering the regulator and interfering with the 
proper operation of the regulator.

Maximum Inlet Pressures

Содержание 441-S

Страница 1: ...RM 1350 R7 Sensus Metering Systems Installation and Maintenance Instructions Model 441 S Regulator T H E G A S I N D U S T R Y ...

Страница 2: ...e larger size The 1 2 union 60 contains a small orifice approximately 1 16 diameter This orifice should not be removed Also make certain this orifice is open and free of foreign material Check all connections for leaks CAUTION Turn gas on very slowly If an outlet stop valve is used it should be opened first Do not overload the diaphragm with a sudden surge of inlet pressure Monitor the outlet pres...

Страница 3: ...a few turns 50e or 50i screws into 24 but should be loose by 1 2 to 1 turn 3 If orifice 29 was removed reinstall it 4 Inset lower valve assembly and screw into place by a few turns 50h screws into 50e 5 Turn upper valve assembly so Allen screw 50g is accessible through side inspection opening 6 Make the valve lock up adjustment as follows a Hold upper valve against its seat This can be done by han...

Страница 4: ...usted using the correction factors on page 5 4 Installation and Maintenance Instructions Model 441 S Regulator To Change Spring 1 Remove seal cap 1 back off adjusting screw 10 remove housing cover 5 and remove spring 14 2 Insert the new spring Be sure it nests correctly onto part 15 3 Complete as per steps 7 8 and 9 under To Assemble 441 S To Service Diaphragm 1 Remove seal cap 1 back off adjustin...

Страница 5: ...150 20 20 14 Diaphragm 090 72 150 20 16 Diaphragm 090 73 150 20 18 Diaphragm 090 74 150 20 20 Diaphragm 090 75 150 20 23 O Ring 11 16 I D 7 8 O D 934013 24 Diaphragm Connecting Stem 090 16 058 00 stainless steel 41 Hex Steel Nut 3 8 16 920853 42 Hex Cap Screw 3 8 16 x 1 3 8 Lg 903568 45 Travel Indicator Assembly 5 Installation and Maintenance Instructions Model 441 Regulator 2 Model 441 S Illustra...

Страница 6: ...0a Valve Retaining Nut 5 8 18 905564 2 and 3 Model 441 S continued Illustration Part Number Description Number Valve Retainer standard steel 1 3 4 090 16 018 00 Valve Retainer standard 090 16 018 30 stainless steel 1 3 4 Valve Retainer v port wings 090 16 012 53 stainless steel 1 3 4 50b Valve Retainer standard steel 090 16 018 01 1 1 2 Valve Retainer standard 090 16 018 31 stainless steel 1 1 2 V...

Страница 7: ... plated steel 090 22 028 02 2 1 8 Inlet Orifice stainless steel 090 22 028 52 1 3 4 Inlet Orifice plated steel 090 22 028 01 1 3 4 Inlet Orifice stainless steel 090 22 028 51 3 Outlet Orifice plated steel 090 22 029 00 3 Outlet Orifice stainless steel 090 22 029 50 29 2 1 8 Outlet Orifice plated steel 090 22 029 02 2 1 8 Outlet Orifice stainless steel 090 22 029 52 1 3 4 Outlet Orifice plated stee...

Страница 8: ...2 1 2 14 1 2 Flanged ANSI 300 10 1 2 12 1 2 14 1 2 Pipe Size D E G M N of 441 S 2 6 24 See 5 7 3 6 24 Table 5 7 4 9 1 2 26 Below 5 8 Sensus Metering Systems 2007 Made in USA 805 Liberty Boulevard DuBois PA 15801 800 375 8875 Fax 814 375 8460 www sensus com Limited Warranty Seller warrants the Goods to be free from defects in materials manufactured by Seller and in Seller s workmanship for a period...

Отзывы: