Regulator Installation and

Maintenance Instructions

243 Service
Regulators

Introduction

The 243 is a large capacity general-purpose gas pressure
regulator.

Its outstanding performance and versatility make it an excellent
choice for use on industrial meter sets, combustion equipment,
boilers, burners, unit heaters, furnaces, ovens and other appli-
cations.

Use it for natural gas, air, dry CO

2

, propane, butane, L.P.G.,

nitrogen, and others.  Special materials are available for cer-
tain corrosive gases.

In addition to the standard models and internal relief models
covered in this bulletin, the 243 is also available with low pres-
sure cut-off, with built-in monitor, and as a pilot operated regu-
lator (outlet pressures to 35 psig), a back pressure valve, a
relief valve, a vacuum regulator and a vacuum breaker.  For
information, please contact your Sensus Sales Office or
authorized industrial distributor.  The 243 is manufactured in
conformance with Code B31.8.

Note: The term standard refers to Non-IRV configurations.

Model Specifications

243-12-1 and 243-12-2

Maximum Inlet Pressure.........................................125 psi
Outlet Pressures......................................3 

1

2

” w.c. to 3 psi

Pipe Sizes................................................ 1 

1

4

”, 1 

1

2

” and 2”

Diaphragm..................................... 12” (nominal diameter)

243-8-1 and 243-8-2

Maximum Inlet Pressure.........................................125 psi
Outlet Pressures..................................3 

1

2

” w.c. to 4 

1

4

” psi

Pipe Sizes................................................ 1 

1

4

”, 1 

1

2

” and 2”

Diaphragm....................................... 8” (nominal diameter)

243-8HP

Maximum Inlet Pressure.........................................125 psi
Outlet Pressures................................................3 to 10 psi
Pipe Sizes................................................ 1 

1

4

”, 1 

1

2

” and 2”

Diaphragm....................................... 8” (nominal diameter)

Maximum Inlet Pressures

* Applies only to 243-12 with external control line.

t

80 psi for 243-12 with external control line

Temperature Limits

The Model 243 Service Regulators can be used for flowing
temperatures from -20 F to 150 F.

Buried Service

The Model 243 Service Regulators are 

not

recommended for

buried service.

Installation and Start Up

(See Illustrations on Page 3.)

1. Make certain that regulator and piping are free of dirt,

moisture, foreign matter and other debris.

2. Be sure all shipping screens or covers are removed and

regulator is installed with flow in correct direction.

3. Regulator may be installed in any position; right-side-up, up- 

side down, vertical pipe, horizontal pipe, diagonal pipe, etc.

By loosening union bolts 

(16)

, the diaphragm case assembly

may be rotated to various positions in relation to the body.
Make certain 

(16)

are re-tightened to hold diaphragm case

assembly in new position and to reseal.

CAUTION

The diaphragm case vent must be positioned

to protect against flooding, drain water, ice

formation, traffic, tampering, etc. The vent

must be protected against nest building

animals, bees, insects, etc. to prevent vent

blockage and minimize the chances for

foreign material from collecting in the vent

side of the regulator diaphragm.

4. Make sure there are no leaks and all connections are firm
and tight. Tighten flange bolts evenly and firmly. On screwed
connections apply pipe dope to male threads only.

5.  On regulators arranged for External Control Line, run pipe
or tubing from 

1

2

” NPT connection in lower case to the con-

trol connection in the outlet piping.  This control piping
should not be less than 

1

2

” in size and should be adequately

protected against breakage (regulators go wide open if the
control line is broken).  In general, the control connection
should be at least 8 pipe diameters from the regulator and in
as straight a run of pipe as possible.  The connection itself
must be smooth on the inside of the pipe.  Pitch the control
line away from the regulator and avoid moisture pockets.
Keep inside of control line clean.  Never install any type of
automatic shut-off device, which closes completely, between
the regulator outlet and the control line connection.

CAUTION

It is the user’s responsibility to assure that all

regulator vents and/or vent lines exhaust to a

non-hazardous location away from 

any potential

sources of ignition. Where vent line are

used, it is the user’s responsibility to assure

that each service regulator is individually vented

and that common vent lines 

are not 

used.

6. Adjust outlet pressure (set point) by removing cap 

(1)

or

(1e)

and turning adjustment spring button 

(3)

. On 243-8 HP

remove cap 

(1a)

, loosen locknut and turn adjustment screw

(1b)

. Turn clockwise to increase and counter-clockwise to

decrease outlet pressure.  Only adjust when gas is flowing
through regulator.  When adjustment is completed, seal cap

(1)

or 

(1e)

must be securely screwed into place.  The

absence of this seal cap can result in unstable operation.

243-12

15 psi
25 psi
25 psi
40 psi
40 psi
60 psi

100 psi
125 psi
125 psi

• • •

243-8

• • •
• • •

25 psi

25 psi
40 psi
40 psi
80 psi

100 psi
125 psi
125 psi

1

1

4

” - 30

1

1

4

” - 10

1” - 30
1” - 10

3

4

” - 30

3

4

” - 10

1

2

” - 10

3

8

” - 10

1

4

” - 10

.207” - 10

t

ORIFICE SIZE - VALVE

O

O

O

O

O

O

O

O

O

O

O

O

*

*

Содержание 243-12-1

Страница 1: ... to various positions in relation to the body Make certain 16 are re tightened to hold diaphragm case assembly in new position and to reseal CAUTION The diaphragm case vent must be positioned to protect against flooding drain water ice formation traffic tampering etc The vent must be protected against nest building animals bees insects etc to prevent vent blockage and minimize the chances for fore...

Страница 2: ...icing make certain that regulator installation is entirely free of leaks CAUTION Regulators are pressure control devices with numerous moving parts subject to wear that is dependent upon particular operating conditions To assure continuous satisfactory operation a periodic inspection schedule must be adhered to with the frequency of inspection determined by the severity of service and applicable l...

Страница 3: ...5 lb FF 1 1 4 1 1 2 and 2 screwed Drilled and Tapped 1 2 NPT on regulators arranged for External Control Line STANDARD DIAPHRAGM ASSEMBLY INTERNAL RELIEF VALVE Drilled and Tapped 1 2 NPT on regulators arranged for External Control Line THROAT BLOCK WITH O RING SEAL for regulators arranged for External Line Control 1 2 3 4 5 8 9 10 1 1d 1 1f 13 1 1k 1 1b 1 1a 16 20b 21 24 1e 2a 25 27 26 25 1 1d 1 1...

Страница 4: ...alone This applies with the monitor located either up or downstream SPRING COLOR Red Red Black Blue Blue Black Green Black Green Orange Black Orange Black Cadmium Cadmium Cadmium White t PART NUMBER 143 16 021 03 143 82 021 00 143 16 021 04 143 82 021 01 143 82 021 02 143 16 021 05 143 16 021 11 143 16 021 06 143 16 021 07 143 16 021 08 143 16 021 08 143 16 021 08 143 16 021 13 243 12 3 1 2 to 6 1...

Страница 5: ...0 8 000 11 000 15 000 18 000 21 000 22 000 19 000 15 000 5 400 7 000 8 500 10 500 14 500 18 000 20 000 22 000 19 000 15 000 6 800 8 600 10 500 13 000 20 000 25 000 25 000 25 000 19 000 15 000 O O O O O O O O O O O O O O O O O O O O O O O O O INLET PRESSURE psi ORIFICE SIZE AND VALVE ANGLE 6 w c RED BLACK SPRING 1 w c droop 7 w c BLUE BLACK SPRING 1 w c droop 18 w c GREEN SPRING 3 w c droop 1 psi O...

Страница 6: ...ods which have been i repaired altered or improper ly installed ii subjected to improper use or storage iii used or incorporated with other mate rials or equipment after Buyer or anyone using the Goods has or reasonably should have knowledge of any defect or nonconformance of the Goods or iv manufactured fabricated or assembled by anyone other than Seller c shall not be effective unless Buyer noti...

Отзывы: