The outlet of the vent piping must allow for free and 
unobstructed passage of air and gas and must be protected 
against the potentials listed in instructions #4, #8 and #9.

10.

For outdoor installations, it is recommended that the regulator 
be installed so that the regulator vent faces downward to avoid
the potential for water and other foreign matter entering the 
regulator and interfering with the proper operation of the 
regulator. 

CAUTION:

Regulators are pressure control devices with numerous moving 
parts subject to wear that is independent upon particular operating
conditions. To assure continuous satisfactory operation, a periodic
inspection schedule must be adhered with the frequency of 
inspection determined by the severity of service and applicable
laws and regulations.

Servicing 

1.

To access valve 

7

, orifice 

6

, or diaphragm assembly 

8

first remove spring compression by unscrewing the 
spring cap 

and spring adjustment ferrule 

2

Remove spring 

3

from regulator.

2.

For access to the valve

7

and orifice

6

, completely loosen 

the coupling nut 

12

and remove diaphragm case assembly 

from body 

5

.

3.

To replace Buna-Nitrile valve pad 

7

, simply pull off of valve 

stem 

9

and replace with new pad. 

4.

To replace orifice 

6

, unscrew from body using a 1" hex 

socket wrench “thin-wall” type. Apply sealant on threads of 
orifice when installing replacement orifice. Re-screwing 
replacement orifice must be installed at 50-60 ft-lbs. of torque.  

5.

To replace diaphragm assembly, remove flange screws 

10

and disassemble diaphragm assembly. Make certain all parts 
are reassembled in their correct order and all threads and 
joints are tightened evenly and firmly.

6.

Before reassembling body to diaphragm case, make certain 
that the o-ring is in position. 

Over Pressurization Protection 

Protection must be provided for the downstream piping system 
and the regulator's low pressure chambers to assure against 
the potential for over pressurization due to a regulator malfunction 
or a failure of the regulator to lock up. The allowable over-
pressurization is the lowest of the maximum pressures permitted
by federal codes, state codes, Sensus Bulletin RDS-1498, 
or other applicable standards. The methods of providing over-
pressure protection could be a relief valve, a monitor regulator, 
a shut-off valve or similar device.

Buried Service

The Model 143-80 regulator is not recommended for buried 
service.

Temperature Limits

The Model 143-80 regulator can be used for the flowing 
temperature of -20°F to 150°F (-28.9°C to 65.5°C).

Maximum Emergency Pressures

The maximum pressure the regulator inlet may be subjected under 
abnormal conditions without causing damage to the regulator is:
Maximum Inlet Pressure plus 50 psi.

The maximum pressure to which the regulators case may be 
subjected under abnormal conditions without causing damage 
to the internal parts is: Set point plus 3 psi. If the outlet pressure
exceeds this pressure, the regulator must be removed from service
and carefully inspected. Damaged or otherwise unsatisfactory
parts must be replaced before returning the regulator to service.

The maximum outlet pressure that can be safely contained in 
the diaphragm case is 10 psi (safely contained means no leakage
as well as no bursting.)