SPECIFICATIONS

Kit Number

6-920-UG-3

Type

Three Phase Underground Recording Ammeter Kit

3 ea Amcorder UG

1 ea IrDA Serial Cable

1 ea Soft Carrying Case

1 ea Softlink Software

Range of Operation

 Voltage

69 

kV

 

Current

1 to 2000 A

Resolution

 Amps 

0.1 

A

Accuracy

 

Amps

± 1%, ± 2 Counts

Frequency, 50 Hz

47 to 53 Hz

Frequency, 60 Hz

57 to 63 Hz

Mechanical

 

Weight

1.8 lbs, 0.82 kg

 

Sensor Opening

up to 2.5 in, 6.35cm

 

Dimensions

8.87 in x 5.38 in x 3.74 in, 22.3 cm x 13.7 cm x 9.5 cm

 

Housing

Shock and water resistant molded urethane

 

Operating Temperature

-22 to +140˚ F, -30 to +60˚ C

Lithium battery required for temperatures below -4°F (-20°C). 

 

Submersible

Submersible to 6 ft of water to IPX8

 

Hotstick Mounting

Shotgun Style Hotstick (Hotstick not included)

 

Battery

9 Volt Alkaline or Lithium

Software Requirements

Softlink for SensorLink

 

Processor

100 Mhz or Higher, 200 Mhz Recommended

 

RAM

32 MB, 64 MB Recommended

 

Drive Space

15 MB to Load Software, 10 MB Operating Space

Data Collection Space

64,000 Data points

Page 4

Содержание 920-UG

Страница 1: ...SensorLink Operators Manual Recording Ammeter Amcorder UG...

Страница 2: ...Model 920 UG Qty 1 sold in 6 920 UG 1 Kit Qty 3 sold in 6 920 UG 3 Kit Carrying Case Model 659 UG Qty 1 sold in 6 920 UG 1 Kit Qty 1 sold in 6 920 UG 3 Kit USB IrDA Dongle Model 7 021B Qty 1 sold in...

Страница 3: ...mple and Log Intervals 6 Battery Replacement and Operation 7 Installation of Amcorder UG 8 Removal of Amcorder UG 9 Submersed Applications 10 Warranty 19 Quality Assurance Back Cover SoftLink Software...

Страница 4: ...5cm Dimensions 8 87 in x 5 38 in x 3 74 in 22 3 cm x 13 7 cm x 9 5 cm Housing Shock and water resistant molded urethane Operating Temperature 22 to 140 F 30 to 60 C Lithium battery required for temper...

Страница 5: ...he cover plate chuck and entire Amcorder are to be considered at the same potential Putting the cover plate chuck or other parts of the Amcorder within the air gap of adjacent phases or ground could c...

Страница 6: ...e Recorder should be cleaned by wiping with a silicone hot stick wipe to remove dirt sand and salt that will degrade the urethane housing Sample and Log Intervals Sample and Log Interval The Sample In...

Страница 7: ...Recorder will stop operating when the battery fails to supply more than five volts All the logged data is safely stored in flash memory When a fresh battery is put into the Recorder the user has five...

Страница 8: ...3 Place the Amcorder UG on the conductor beneath the elbow and above the concentric neutral It does not matter if the clamp is facing upwards as shown below in step four or downwards Step 4 Push the u...

Страница 9: ...elbow off the bushing pull from the side or use a second hot stick to hold the elbow in place Submersed Applications When placing the Amcorder UG in an application where it may become submersed in wa...

Страница 10: ...mission and instructions to complete the install if drivers are not installing automatically Softlink Installation Step 1 Softlink Installer is available at www sensorlink com products amcorder Save t...

Страница 11: ...ommunicating with Recorder Softlink communicates with one Recorder at a time To make sure only one Recorder is communicating stand any other Recorders on their base To communicate with a Recorder foll...

Страница 12: ...bar Battery life depends on this setting see page four Synchronization Selecting the Clear all logged data from the Recorder and synchronize logging to the hour box will allow the Recorder to synchron...

Страница 13: ...e data from any additional units Each unit s data will load into a new tab NOTE Once a fresh battery is inserted the user has 5 minutes to start downloading the data before the Amcorder resets itself...

Страница 14: ...uture review in Softlink or another data management program The data from each recorder is saved into its own file Step 1 Select the data file by selecting the Recorder on the menu Step 2 Select save...

Страница 15: ...opening saved files Step 1 Open Softlink Step 2 Close the Discovering ports and instruments bar Step 2 Select Open File Step 3 Find and select the csv or xlsx Softlink file Opening data files in other...

Страница 16: ...ickness The thickness of the graph lines can be changed by the user Thickness is numbered 1 10 and defaults at three The software will show a preview to the user as the value is changed Chart spline t...

Страница 17: ...asurement parameters will display on the graph Hide and Show Report Options Click the left arrow to hide Report Options Click the right arrow to show the hidden Report options Zoom Window The bottom g...

Страница 18: ...ork The IrDA you received with your kit has been tested to work with the Recorders 5 The Serial Number of the IrDA must start with a TA if running Softlink on WIN 10 6 Try restarting Softlink by first...

Страница 19: ...f the instrument 2 Subjected to misuse negligence or accident or 3 Connected installed adjusted or used otherwise than in accordance with the instructions furnished by SensorLink Corporation This Warr...

Страница 20: ...________ I hereby certify that the Model 920 UG Amcorder UG s have has passed all tests defined in the SensorLink Corporation standard I also certify that I have reviewed the standard and test procedu...