16 

unique, i.e. the devices connected to one line of power and communication must not have 
the same addresses.  

Note 

– The signal device default address (set by Manufacturer) is 88. It is recom-

mended to set the signal device address within the range from 82 to 92. 

If signal device address is unknown, then input of 255 addresses (self-request) shall 

enter the signal device configuration settings. 

Viewing  or  altering  of  address  shall  be  performed  in  accordance  with  2.4.4.1, 

2.4.4.2: 

-

 

enter transducer configuration menu; 

-

 

Scroll to and select 

inFo 

menu item; 

-

 

scroll  to 

Ad

  sub-item,  current  value  of  address  shall  be  displayed  on  the  indicator 

board;  

-

 

- to change, enter 

Ad

 sub-

item and type new transducer’s address;  

-

 

scroll to 

End

 item and exit with saving changes. 

The  controller  software  number  is  pointed  in 

inFo 

menu  item.  Controller  software 

number shall be displayed when 

Pn 

parameter is chosen.

 

2.4.3 configuration of devices; 

Adjustment  of  other  devices  is  executed  similar  to  the  signal  device  adjustment. 

Each device has individual menu items, shown in device Operation Manual.  

Configuration  of  different  devices  can  be  carried  out  simultaneously  with  several 

signaling devices in the line; SENS measuring system is capable for operation during con-
figuration.  It  is  not  acceptable  to  adjust  the  device  (using  certain  signal  device)  that  is  al-
ready being adjusted or interrogated by other signal device in the same time. 

Warning!  If  0  address  is  used  for  configuration,  only  one  device  can  be  con-

nected  to  the  signaling  device,  otherwise  other  devices  can  be  reprogrammed  by 
accident  (this  can  affect  address  and  other  settings),  i.e.  only  two  devices  with  ad-
dress shall be in the line - the signaling device and a device with unknown address.  

2.4.4 INDICATION OF ERRORS 

In  case  of  any  extraordinary  event  occurrence  (missing  connection,  unknown  pa-

rameter  receiving,  etc)  signal  device  informs  the  operator  and  displays  the  errors  on  the 
screen. Possible mistakes and their reasons are pointed in table 2.4. 

Table 2.4 

Indication 

Cause 

Er.tr 

No connection with device (line break, device failure). 

Err 

The transducer cannot measure set for viewing (transducer failure). 

EPrr 

The device returned parameter that is unknown for signal device (a new 
device  was  applied  in  the  system,  outdated  version  of  controller  soft-
ware). 

EE 

Displayed  instead  of  address  set  for  viewing  if  address  value  is  more 
than 99 

3 MAINTENANCE  

3.1 Technical  maintenance  includes  preventive  and  operation  check  works.  Tech-

nical  maintenance  is  performed  in  order  to  ensure  operational  capability  and  save  trans-
ducer operation and technical features within its full lifetime. 

3.2 It is necessary to follow maintenance instructions specified in cl. 3.1. 
3.3 Preventive measures include: 
Inspection  and  check-up  of  exterior.  It  includes  checking  of  mechanical  damages 

absence,  marking  integrity,  strength  of  signal  device  parts,  absence  of  signal  device  sur-
face contaminations. 

Содержание SENS MS-K-500-3

Страница 1: ...Research and production enterprise SENSOR SENS device Signaling device MS K 500 3 MS K 500 3S Operation Manual ...

Страница 2: ... Technical specifications 3 1 3 Completeness 3 1 4 Design and operation 4 1 5 Marking 6 2 1 Safety measures notification 6 2 2 Operational limitations 6 2 4 Used items 8 3 MAINTENANCE 16 4 ROUTINE PRODUCT REPAIR 17 5 TRANSPORTATION AND STORAGE 17 6 UTILIZING 17 7 ANNEX A 18 ...

Страница 3: ...he range from minus 5 up to 50 C or S3 as per GOST R 52931 2008 1 2 Technical specifications 1 2 1 Mechanical impact resistance of MS K 500 3 and MS K 500 3C signal device corresponds to V1 as per GOST R 52931 1 2 2 Water and dust ingress protection degree of the signal device is IP54 accord ing to 1 2 3 Normal functioning of the signal device can be provided if the length of power and communicati...

Страница 4: ...llowing devices are installed under the signal device cover Record protection toggle 10 piezoelectric ring 6 and terminal clamp 8 designed for external circuits connec tion 1 housing 2 cover 3 cable fitting 4 looking glass 5 exterior panels 6 piezoelectric ring 7 control button 8 terminal clamp 9 installation orifice 10 record protection toggle 11 silicone gasket 12 protective sealing orifice 13 n...

Страница 5: ...signal device is config ured on reaction for certain events occurrence then if the event occurred certain status byte received the indicator displays the device address designation and value of the pa rameter the indication is glowing In accordance with operator s actions the signal device in operation mode interro gates the devices connected to a SENS line and displays the parameters set by the o...

Страница 6: ...f BK shall be only performed with power supply disconnected 2 2 Operational limitations 2 2 1 Use of a signaling device with mismatching power supply voltage is not al lowed 2 2 2 List of critical failures of signaling devices is given in table 2 1 Table 2 1 Failure Cause Actions A device is not op erable Mismatching power sup ply voltage Check and bring into accordance Power and or control circui...

Страница 7: ...k For operation check it is required to supply power on a signal device within 1 5 se conds signal device should emit one short sound signal Then signal device shall be switched to an operation mode or a sleep mode the flashing dot or a last interrogated sensor address shall appear on the screen In case of sound signal missing or wrong indi cation on the screen signal device should be deemed as ma...

Страница 8: ...king 9 2 3 5 After wiring it is required to configure signal device in accordance with a spe cific application It is necessary to check the accordance of settings recorded in configura tion data sheet for specific application and if necessary adjust the configuration Configu ration is made in accordance with cl 2 4 2 All changes must be recorded in configuration data sheet 2 3 6 Check operational ...

Страница 9: ...pressure Picture 2 3 Scrolling from one parameter to the other is executed by short pressing of the signal device right button Scrolling to next device parameter view is executed by long pressing or short pressing of the right button of signal device picture 2 4 Long press inscrease value Short press select parameter back left Long press decrease value Both buttons 1 go to settings mode 2 back und...

Страница 10: ...y carried out by the Manufacturer according to the purchase order data The reconfiguration of the signal device during operation may be needed if the purchase order data was incomplete or mismatching Signal device in configuration mode does not affect functionality of other devices in the line at the same time it neither interrogates transducer nor reacts on reaching of criti cal level Signal devi...

Страница 11: ...o exit without saving changes indica tor boards will show message no no saving End Any changes Err S SAV Back to menu Not saved Yes No Save No changes no Not saved cancelled Er tr Device not responding YES Save Saved t Wait Picture 2 7 If the saving reading calibration etc operations requires more than 1 second the screen will display t in the main field and Wait in the information field picture 2...

Страница 12: ...t d1 1 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адрес 002 Отступ от дна резерв SEtt d0 9 200м ПМП 201А Адрес 002 Отступ от дна резерв SEtt d0 9 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адре...

Страница 13: ...peration mode End End Br Picture 2 11 List of items sub items and configuration menu parameters is listed in table 8 3 Table 2 3 N o Item sub item parameter Note Desig nation Name Des ignati on Name unit of measure ment 1 SEE Not used 2 SEtt Main configurable parameters F Interrogation period s Set in accordance with 2 4 4 3 3 Br Indicator brightness 4 S SEE Table of devices set for viewing 1 n Se...

Страница 14: ...or brightness adjustment Brightness value ranges from 0 to 100 The more the Br value the more the bright ness It is recommended to set the middle brightness level value because the operation within the highest brightness values shall reduce the lifetime of OLED screen 2 4 4 2 Configuration table of viewed devices S SEE menu sub item provides adjustment of parameters set for viewing in opera tion m...

Страница 15: ...t will be flashing Set the required reaction short line event is ignored long line reaction is set Scroll to End item and exit with saving changes To delete devices from table it is required to perform the following actions Choose the record subjected for removal Change the device address to 00 Scroll to End item and exit with saving changes Notes 1 Device addresses are sorted automatically by inc...

Страница 16: ...interrogated by other signal device in the same time Warning If 0 address is used for configuration only one device can be con nected to the signaling device otherwise other devices can be reprogrammed by accident this can affect address and other settings i e only two devices with ad dress shall be in the line the signaling device and a device with unknown address 2 4 4 INDICATION OF ERRORS In ca...

Страница 17: ...depending on operating conditions 4 ROUTINE PRODUCT REPAIR 4 1 Product repair is replacement of broken parts and units it can be carried out by organization granted to do repair of explosion proof equipment Spare parts are supplied by the manufacturer 5 TRANSPORTATION AND STORAGE 5 1 Transportation conditions shall correspond to GOST 15150 69 at medium tem perature range from 50 C to 50 C Transpor...

Страница 18: ...ation conditions as to environment climatic as pects influence 1 1 2 5 1 5 2 GOST 30852 13 2002 IEC 60079 14 1996 Explosion proof electrical apparatus Part 14 Electrical installations in explosive gas atmos pheres other than mines 2 1 2 GOST 30852 16 2002 IEC 60079 17 1996 Explosion proof electrical apparatus Part 17 Inspection and maintenance of electrical installa tions in hazardous areas other ...

Страница 19: ...19 NPP SENSOR LLC RUSSIA 442965 Zarechny Penza region P O Box 737 phone fax 7 841 2 65 21 00 7 841 2 65 21 55 Corr 21 10 2019 ...

Отзывы: