3.1  Connection relays outputs

To connect relays, see the board layout described in Figure 2. It’s important to consider these 

explanations: NC stays for normally closed, NO indicates a contact normally open and COM 

is the common contact. The gas detector has the relay 1 associated to the firs alarm thresh-

old and the relay 2 to the second threshold as default setting. The user can set different con-

nections, as described in Figure 2. It’s possible to connect both the alarm thresholds at the 

same relay, the association of the same event to both relays is highly discouraged.

When correctly set, SMART3R LITE can be installed in systems with a functional safety SIL2.  

In order to guarantee this capability the following settings must be implemented

•  Relays must be set as normally energized (JP27 open)
•  Connect to a relay only the fault event (close PIN 1-2 of JP26 or JP28)
•  Duringt installation step, connect a 1.33A fuse to each relay’s output
•  Check the relays functionality at least one time per year, by testing detector response 

with gas application and checking the relays activation

The following table describes the safety parameters related to the relays outputs: 

SFF

PFD

λsd [1/h]

λsu [1/h]

λdd [1/h]

λdu [1/h]

T1

MTTR

94,10%

2,09E-04 3,80E-10

2,94E-07

4,26E-07

4,52E-08

1 anno 24h

3.2  Connection serial line RS485 (optional) 

The connection of SMART3R LITE to RS485 bus lines should be performed by using a 4-wire 

cable, 1 pair for the RS485 bus and 1 for the power supply. It is also necessary that:

•  Wiring between the detectors and the control panel should be made by using con-

nection cable EIA RS485: 2 core wires with section 0.22 / 0.35 mm2 and shield (twisted 
pair). Nominal capacity between the wires <50pF/m, nominal impedance 120 Ω. These 
features can be found in BELDEN cable 9842 or similar (data transmission cable in EIA 
RS485).

•  Using this wiring, the total length of the line should not exceed 1000 m.
•  Detectors are to be wired in daisy chain mode. We recommend avoiding star or tree 

mode connection as interference immunity would be reduced. 

•  Make sure that each multi-polar wire includes just one RS485. 
•  Make sure that a 120 Ω end line resistor is placed at the beginning and at the end (on 

the last detector) of the bus line.

•  For the detectors’ power supply connection, we recommend using a 2-wire cable with 

suitable section according to the distance and number of detectors. 

•  Once the installation has been completed, verify that each detector reaches at least 

12 Vdc.

Содержание S3832R32

Страница 1: ...Manuale d istruzione Instruction Manual MT4647 rev 3 01 07 2022 2021 SENSITRON S R L All rights reserved www sensitron it Rilevatore per gas refrigeranti Detector for refrigerant gas SMART3R LITE...

Страница 2: ...for any additional information relative to use or repair QUESTO MANUALE DEVE ESSERE LETTO ATTENTAMENTE DATUTTI COLORO CHE HANNO O AVRANNO LA RESPONSABILITA DI INSTALLARE UTILIZZARE O DI PRESTARE UN S...

Страница 3: ...intenance 19 5 Accessories 20 6 Warranty coupon for repairing 21 7 Instructions for disposal 22 SOMMARIO 1 Introduzione 1 1 1 Descrizione generale 1 1 2 Codici prodotto 2 2 Caratteristiche tecniche 3...

Страница 4: ......

Страница 5: ...5 2 40 Annex LL ISO 5149 3 Il rilevatore ha una custodia in policarbonato con due pressacavi M20 sui lati sono presenti delle guide preformate che possono essere forate per aggiungere fino a sei press...

Страница 6: ...S3862R454C Rilevatore per R454C soglie al 5 e 10 LFL S3863R452B Rilevatore per R452B soglie al 5 e 10 LFL S3835R134A Rilevatore per R134A soglie 1000 e 2000 ppm S3836R410A Rilevatore per R410A soglie...

Страница 7: ...Sale macchine e impianti di refrigerazione Sensore Infrarosso Vita stimata del sensore 5 anni Gas rilevati R32 R1234YF R1234ZE R454A R454B R454C R452B R134A R410A R404A R407C CO2 Fondoscala 0 20 LFL...

Страница 8: ...4 1 1 JP5 CONNETTORE PER SCHEDA RS485 OPZIONALE SCHEDA RS485 OPZIONALE JP4 CHIUDERE SOLO SE IL RILEVATORE L ULTIMO DELLA LINEA SERIALE RS485 JP4 CHIUSO INSERITO TERMINATORE DI LINEA JP4 APERTO TERMINA...

Страница 9: ...s posti in zone nelle quali siano presenti vibrazioni e sebbene immuni da disturbi a radiofrequenze consigliabile non installarle in pros simit di emettitori radio ponti radio o apparecchiature simili...

Страница 10: ...dei rel La tabella seguente riporta i dati di affidabilit del rilevatore considerando come uscita di sicurezza le uscite rel SFF PFD sd 1 h su 1 h dd 1 h du 1 h T1 MTTR 94 10 2 09E 04 3 80E 10 2 94E 0...

Страница 11: ...Uso Il rivelatore funziona automaticamente e autonomamente pertanto non richiesto alcun contributo da parte del suo utilizzatore I LED frontali indicano lo stato in cui il rilevatore si trova Tabella...

Страница 12: ...ra di calibrazione permette di eseguire Taratura di Zero Taratura dello Span Reset del dispositivo Modifica o sola visualizzazione del Baud Rate Impostazione dell indirizzo del bus RS485 Visualizzazio...

Страница 13: ...garanzia sui prodotti Sensitron valida un anno dalla data di fabbricazione riportata sul prodotto Si intende valida comunque per un anno dalla data di installazione purch la stes sa avvenga entro i do...

Страница 14: ...ssa in qualsiasi forma o con qualsiasi mezzo inclusi fotocopie registrazioni o altri metodi elettronici o meccanici senza la previa autorizzazione scritta di Sensitron 7 Istruzioni per lo smaltimento...

Страница 15: ...ITALIANO Pag 11...

Страница 16: ...ENGLISH Pag 12...

Страница 17: ...nnex LL ISO 5149 3 The plastic enclosure has two M20 cable glands and on the sides there are pre formed guides that can be drilled to add up to six M16 cable glands The circular plastic contour offers...

Страница 18: ...etector alarm thresholds 5 and 10 LFL S3863R452B R452B detector alarm thresholds 5 and 10 LFL S3835R134A R134A detector alarm thresholds 1000 and 2000 ppm S3836R410A R410A detector alarm thresholds 10...

Страница 19: ...on plants Sensing element Infrared Predicted sensor life 5 years Gas detected R32 R1234YF R1234ZE R454A R454B R454C R452B R134A R410A R404A R407C CO2 Fullscale 0 20 LFL 0 5000 ppm Alarm thresholds 5 a...

Страница 20: ...TIONAL Jp4 CLOSED ONLY IF THE DETECTOR IS THE LAST ON THE RS485 SERIAL LINE JP4 CLOSED LINE TERMINATOR ENABLED JP4 OPEN LINE TERMINATOR DISABLED 24V GND JP1 A B 1 GREEN ACTIVITY LED DL1 RELAY 2 JP26 J...

Страница 21: ...with the electro magnetic compatibility rules it is advised to keep the detectors at a distance from any radio frequency senders such as radio links or similar Please be also sure that detectors are...

Страница 22: ...safety parameters related to the relays outputs SFF PFD sd 1 h su 1 h dd 1 h du 1 h T1 MTTR 94 10 2 09E 04 3 80E 10 2 94E 07 4 26E 07 4 52E 08 1 anno 24h 3 2 Connection serial line RS485 optional The...

Страница 23: ...intenance 4 1 Power ON When the detector is powered on the LEDs start blinking yellow during warmup time After one minute the LEDs remain green during normal status Once the warm up phase is over the...

Страница 24: ...es the following Zero calibration Span calibration To reset the device To change or visualize only the Baud Rate To set the address of the RS485 bus To show the firmware version of the detector Stainl...

Страница 25: ...will be considered the stamp and date of the installer placed on the present coupon which is to be duly kept by the user and returned to the installer in case of any working tests and repairs Use one...

Страница 26: ...d to Sensitron Sensitron has a policy of continuous development and improvement of its products As such the specification for the device outlined in this document may be changed without notice In case...

Страница 27: ......

Страница 28: ...actdetails SENSITRONs r l Viale della Repubblica 48 20007 Cornaredo MI Italy TEL 39 0293548155 FAX 39 0293548089 www sensitron it E mail sales sensitron it LEADER IN SIL2 SIL3 FIXED GAS DETECTION SYST...

Отзывы: