SenseAir tSENSE VAV No Disp Скачать руководство пользователя страница 4

 

 

 

 

 

Document 
UMA 192 

Rev 

Page 
4 (12)

 

 

 

 

Figure 3: Screw Terminal 

 

 
The  sensor  is  supplied  with  0  -  10VDC  linear  analogue  outputs  for  Out(1),  Out(2)  and  Out(3)  (see 
Table  1).  Alternative  output  ranges  can  be  configured  via  PC  software  UIP  (version  5  or  later).  See 
information at 

senseair.com. 

 

Out1/Out2/Out3 

e.g

 

 
Each output consists of four blocks. Each block has nine source options. 
OUT1 (OUT2/ OUT3/(Relay)) is the 

largest

 (Max of a, b , c) demand from Proportional-bands. 

 
OUT1=Max of Out1_a/ Out1_b/ Out1_c minus (sub) Out1_d 
5V (Out1_c) 

– 0V (Out1_d Disabled) = 5V 

=>

 OUT1=5V 

 
The (e.g.) VAV valve opens from minimum set-point position with full opened state at the maximum 
set-point.

 

 

 
U

Out

 = 0V 

if space has the value:

 

 
U

Out

 will be increased 

if space has the value:

 

 
U

Out

 = 10V 

if space has the value:

 

 
CO

2

 

≤ 600ppm  

and 

Temp 

≤ 22°C

 

and  

RH 

≤ 75%RH 

(Out1_d = Disabled)

 

 
600ppm 

≤ CO

2

 < 900ppm 

or 

22°C 

≤ Temp < 23°C 

or 

75%RH 

 

RH < 85%RH 

(Out1_d = Disabled)

 

 
CO

2

 > 900ppm 

or 

Temp > 23°C 

or  

RH > 85% 
(Out1_d = Disabled) 

 
e.g. Temp protection (Out1_d) Enabled 

 
OUT1 

=

 10V (Out1_a) 

 10V (Out1_d) 

=

 0V

 

 

UIP5

 

 

 

Out1_a:

 

CO

2

 has a Proportional-band of 600-900ppm 

Out1_b:

 Temp has a Proportional-band of 22-23°C

 

Out1_c:

 RH has a Proportional-band of 75-85%RH 

Out1_d:

 

Disabled

 

 
Out1_a  
CO

2

 = 714ppm =>3V

 

 
Out1_b  
Temp = 22.4°C =>4V

 

 
Out1_c  
Humidity = 80%RH=>5V 

 
Out1_d  
Disabled

 

 
Out1_a  
CO

2

: 1205ppm=> 10V

 

 
Out1_b  
Temp: 16.4°C => 0V

 

 
Out1_c  
Humidity: 80%RH=>5V 

 
Out1_d  
Temp: 16.4°C =>10V 

NOTE!

 (sub) 

(Temp protection) 

Содержание tSENSE VAV No Disp

Страница 1: ...erature and relative humidity in rooms The unit connects to Direct Digital Control DDC Linear outputs are pre programmed as CO2 temperature and relative humidity controller Output parameters can be mo...

Страница 2: ...range 5 Select source 5 Types 5 Proportional band settings 5 Relay 6 Communication settings 6 Address Baudrate 6 Connection configurations 8 Measured values 9 Temperature unit selection 9 Meter inform...

Страница 3: ...0070 Output configurations Terminal Default output Default output range Outputs of this sensor Output ranges of this sensor OUT 1 CO2 Temperature Relative Huminity 0 10 VDC 600 900ppm 22 23 o C 75 85...

Страница 4: ...int position with full opened state at the maximum set point UOut 0V if space has the value UOut will be increased if space has the value UOut 10V if space has the value CO2 600ppm and Temp 22 C and R...

Страница 5: ...P5 Select source Each output consists of four blocks Each block has nine source options UIP5 Source CO2 selected Save Types Analogue Analogue Invert The same approach with Digital Digital Invert UIP5...

Страница 6: ...UIP5 Address UIP5 Baudrate NOTE UIP baudrate RS 485 baudrate if tSENSE VAV No Disp is connected via phone jack see fig 2 UIP baudrate RS 485 baudrate if tSENSE VAV No Disp is connected via screw term...

Страница 7: ...Document UMA 192 Rev 1 Page 7 12 Connect meter Connect meter Information...

Страница 8: ...COM14 USB Serial Port Save Lower right corner of screen NOTE UIP baudrate RS 485 baudrate if tSENSE VAV No Disp is connected via phone jack see fig 2 UIP baudrate RS 485 baudrate if tSENSE VAV No Dis...

Страница 9: ...Temperature unit selection UIP5 Misc Meter information Calibration options CO2 Zero cal Background Target cal UIP If reference meter shows e g CO2 value 500ppm set Target to 500 Background calibratio...

Страница 10: ...y power up Sensor probes are checked constantly during operation against failure by checking valid dynamic measurement ranges System checks returns error bytes to RAM Error codes are available by conn...

Страница 11: ...s Check detailed settings and configuration with UIP software version 5 or later Contact local distributor Table 2 Error codes and action plans NOTE Occurs if probe is out of range at very high CO2 va...

Страница 12: ...r AB Europe SenseAir North America SenseAir Asia Box 96 Stationsgatan 12 SE 82060 Delsbo Sweden 29030 SW Town Center Loop East Suite 202 169 Wilsonville OR 97070 USA SenseAir Chengdu Gas Sensors Ltd F...

Отзывы: