Document
IMA0119
Rev
4
Page
1 (4)
CO
2
transmitter
eSENSE Ind
General
The IAQ-sensor product
eSENSE Ind
for wall mounting in industrial application are
designed to measure carbon dioxide (CO
2
). Option -Disp displays the measured CO
2
value in ppm (parts-per-million) on the LCD.
The units are designed for connecting to Direct Digital Control (DDC) with 0-10V or
2-10V signal inputs. The two parallel signal outputs Out(1) (0-10V) and Out(2) (2-
10V) give linear signal voltages corresponding to the measuring range.
The 2-10V output also indicates the
status
by setting the output voltage to 1V or 2
mA when the sensor self-diagnostics detects any error.
4
5
3
2
1
6
Gas and Air Sensors
eSENSE Ind (Disp)
Installation Manual
1 Wall plate
2 PCB (Factory supplied
mounted in box)
3 Hole for wall plate hooks
4 Snap-in lid
5 Locking screw of the lid
(not shown)
6 Air holes