Intelligent Valve Monitor
Maneuvre Counter
The sensor has a maneuvre counter that works as a maintenance diagnostic, since it allows the user to
schedule preventive maintenance for example when the valve reach the 500 full cycles (opening and closing the
valve). You can view the number of maneuvers via software, in bits 2 and 3 input or there is the possibility of
generating an alarm (via logic programming), warning that should be taken to maintain the valve.
Input Bits
Bit 0
Bit 1
Bit 2
Bit 3
Sensor 1
Sensor 2
Parametre 1
Parametre 2
No. of
Maneuvres
0
0
0 to 499
0
1
500 to 4.999
1
0
5.000 to
49.999
1
1
above
50.000
Output Bitsa
Bit 0
Bit 1
Bit 2
Bit 3
solenoid
Maneuvre counter and
intelligent function reset
Enables intelligent function
not used
0 to 499 Maneuvres
500 to 4.999 Maneuvres
5.000 to 49.999Maneuvres
Above 50.000 Maneuvres
Reset Function
Input and Output Bits Table:
Energy Savings and Solenoid Increased Life Span:
If the solenoid remains activated for more than 1 minute and 30 seconds, the sensor will automatically reduce its
energy-saving voltage source and increasing the life of the solenoid.
Note:
Whenever valve maintenance is performed, the output bit 1 should be activated for at least 1 second to
reset the cycle count.
IMPORTANT!
On the trigger mounting and the control logic
attention should be paid because the sensor 2
should be activated together with the solenoid
command.