| IWR-PORT SERIES
UTILITY OPERATING MANUAL
C
opyright © 2021 Sensata Technologies, Inc.
Page 15
C3 OFF P1 HI P2 HI P3 HI P4 HI P5 HI P6 HI P7 HI P8 HI
This shows that if this is an output, all burnout indications are set to HI. If it is an input,
data values are not affected by any timeout.
The channel being viewed can be changed using the lower or raise buttons, each press
will cause the scrolling message to begin again, for a different channel.
Serial Protocol (14. MODBUS type)
The main menu will display type as either RTU or TCP.
This option allows the serial protocol to be selected. If a different serial protocol is
available, the name of it will be shown in this sub-menu, but it cannot be changed.
MODBUS RTU
(default)
MODBUS TCP
Slave Address (15. ADDRESS address)
The main menu will display the address or unit identifier after ADDRESS
The Modbus slave address or unit identifier can be changed. Selectable addresses are 1
to 247.
The default slave address is 11.
Baud Rate (16. BAUD baud)
The main menu will display the current baud rate after BAUD.
The default baud rate is 9600. Selectable baud rate values are:
4800
9600
(default)
19200
38400
57600
(this should be selected if Ethernet port is used)
Port Settings (17. PORT setting)
The main menu will display the port setting after PORT.
The default port settings are 8 data bits, no parity, 1 stop bit.
Selectable port settings are:
8N1
8 data bits, no parity, 1 stop bit (default)
8N2
8 data bits, no parity, 2 stop bits
8O1
8 data bits, odd parity, 1 stop bit
8E1
8 data bits, even parity, 1 stop bit