![Sensata 24TX60 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/sensata/24tx60/24tx60_owners-instructions-manual_1243174010.webp)
Form: 122189 © 2012 Sensata Technologies
10
6.3 Mounting
6.3.1
Locate a suitable, secure flat mounting surface as close to the 24 volt auxiliary batteries as possible
without being in the same air tight compartment. The maximum recommended distance between the
mounting location and the battery is 10 feet.
6.3.2
The location should provide adequate ventilation and clearance to maintain room temperature while
the unit is operating. At least 1/2 inch of clearance is required on all sides.
6.3.3
Secure the unit with 1/4" screws or bolts in the mounting holes on the legs of the unit.
6.4 DC Wiring
6.4.1
CAUTION:
Assure that hydrogen gas does not accumulate near the battery by keeping the area
well ventilated. A spark may result when connecting the final battery wiring due to initial charging of the
internal input capacitor.
6.4.2
Use stranded copper cable between the battery and the inverter as indicated. Keep the distance to
less than 10 feet. A line fuse must be installed between the battery and the inverter. UL requires that the
fuse be within 18 inches of the battery.
Cable gauge Line fuse
24TX60
4/0 500 amp
6.4.3
Use only an approved fuse holder with a U.L. listed fuse as indicated above.
6.4.4
Using smaller input cable or longer length will greatly degrade the inverter peak performance.
IMPORTANT NOTE FOR VEHICLE INSTALLATION:
Do not use the vehicle chassis as the negative
return in place of a return cable. Use the same size cable as the positive connection and run directly to
the battery.
6.4.5
Install the cables at the battery, inverter and then fuse holder. Make sure that clean, tight
connections are made. Use care not to touch the positive and negative cables together. A violent spark
will result and could result in exploding batteries and fire.
6.4.6
The battery input terminals are located in the wiring compartment. A mounting spark may result
when connecting the battery wire, due to an initial charging of the internal input capacitor.
6.4.7
CAUTION:
Connecting the inverter to the wrong polarity of the battery will cause damage that is not
covered under warranty.
6.4.8
3-phase DC Input Lug Torque; UL 486E states 30 ft/lbs. for brass, therefore, the recommended
torque is or 30 ft. lbs. (360 in. lbs.).