Sensata 24TX60 Скачать руководство пользователя страница 10

Form: 122189 © 2012 Sensata Technologies 

10

 

 

6.3 Mounting

 

6.3.1

 Locate a suitable, secure flat mounting surface as close to the 24 volt auxiliary batteries as possible 

without  being  in  the  same  air  tight  compartment.    The  maximum  recommended  distance  between  the 

mounting location and the battery is 10 feet. 

6.3.2 

The location should provide adequate ventilation and clearance to maintain room temperature while 

the unit is operating.  At least 1/2 inch of clearance is required on all sides. 

6.3.3

 Secure the unit with 1/4" screws or bolts in the mounting holes on the legs of the unit.

               

 

 

6.4 DC Wiring

 

6.4.1 

CAUTION: 

Assure  that  hydrogen  gas  does  not  accumulate  near  the  battery  by  keeping  the  area 

well ventilated.  A spark may result when connecting the final battery wiring due to initial charging of the 

internal input capacitor. 

6.4.2 

Use stranded copper cable between the battery and the inverter as indicated.   Keep the distance to 

less than 10 feet. A line fuse must be installed between the battery and the inverter.  UL requires that the 

fuse be within 18 inches of the battery.  

     

               

 

                             

    Cable gauge    Line fuse

 

            

      24TX60 

 

 

     4/0            500 amp      

 

6.4.3 

Use only an approved fuse holder with a U.L. listed fuse as indicated above. 

6.4.4

Using smaller input cable or longer length will greatly degrade the inverter peak performance.  

 

 

IMPORTANT  NOTE  FOR  VEHICLE  INSTALLATION:

    Do  not  use  the  vehicle  chassis  as  the  negative 

return in place of a return cable.  Use the same size cable as the positive connection and run directly to 

the battery. 

 

6.4.5 

Install  the  cables  at  the  battery,  inverter  and  then  fuse  holder.    Make  sure  that  clean,  tight 

connections are made.  Use care not to touch the positive and negative cables together.  A violent spark 

will result and could result in exploding batteries and fire. 

6.4.6 

The  battery  input  terminals  are  located  in  the  wiring  compartment.    A  mounting  spark  may  result 

when connecting the battery wire, due to an initial charging of the internal input capacitor.

 

6.4.7

 CAUTION:

 Connecting the inverter to the wrong polarity of the battery will cause damage that is not 

covered under warranty. 

 
6.4.8 

3-phase DC Input Lug Torque; UL 486E states 30 ft/lbs. for brass, therefore, the recommended 

torque is or 30 ft. lbs. (360 in. lbs.). 

  
 
 

 

Содержание 24TX60

Страница 1: ...Form 122189 2012 Sensata Technologies 1 DC to AC POWER INVERTERS Quasi Sine Wave 3 Phase Output MODEL 24TX60 OWNER S INSTRUCTIONS...

Страница 2: ...INVERTER MODEL 24TX60 Table of Contents Page 1 Safety Instructions 3 2 Specifications 4 3 Technical Description 5 6 4 Inverter Description 7 5 Status Panel Description 8 6 Installation 9 11 7 Operatio...

Страница 3: ...ray The Inverter System should not be installed in a zero clearance enclosure Damage to the Inverter System will occur if correct polarity is not observed when installing the DC input cables Damage to...

Страница 4: ...ency Better than 85 Other Design Features Vent less for moisture and dust resistance Will withstand vibrating environment Thermally controlled cooling fan Elapsed time hour meter Remote panel with LED...

Страница 5: ...nd and directed into the transformer which steps the voltage up to 120 volts The signal output waveform shape is not sinusoidal it has a total harmonic distortion of 35 and a maximum single harmonic d...

Страница 6: ...ave Heyco strain relief connectors that are to be tightened as follows Sealing nut outside of the DC box is to be at 80 in lbs and the locking nut inside the box is to be set at 60 in lbs The AC cable...

Страница 7: ...Inverter Physical Descriptions 4 1 Inverter Module FIGURE 2 Chassis physical description and installations dimensions FIGURE 3 DC Box See torquing requirements for cover plate round seal goes on outs...

Страница 8: ...a Inverter power Green LED that indicates the inverter is operating from in Inverter Mode b Low battery Red LED that indicates the inverter is in a Low Battery voltage condition c Overload Red LED tha...

Страница 9: ...inch diameter screws to secure the inverter See figure 5 6 2 1 The following instructions should be thoroughly read and understood before installation 6 2 2 CAUTION Inverters produce hazardous voltage...

Страница 10: ...erter UL requires that the fuse be within 18 inches of the battery Cable gauge Line fuse 24TX60 4 0 500 amp 6 4 3 Use only an approved fuse holder with a U L listed fuse as indicated above 6 4 4Using...

Страница 11: ...This model designation has a remote On Off switch circuit modified to accept 12 VDC The remote switch must be connected to the violet wire marked Remote Switch Hookup 6 6 220Y 120 VAC Output 6 6 1 CA...

Страница 12: ...sure the DC wires are clean and tight Check the DC voltage at the inverter DC input Check or bypass the remote On Off circuit Low battery Red LED indicator Indicates that the inverter has shut off du...

Страница 13: ...nsata warrants to the original purchaser for use that the goods or any component thereof manufactured by Dimensions will be free from defects in workmanship from the date of purchase for the period li...

Страница 14: ...Form 122189 2012 Sensata Technologies 14 NOTES...

Страница 15: ...the latest version of the relevant information to verify before placing any orders that the information being relied upon is current Sensata assumes no responsibility for infringement of patents or ri...

Отзывы: