Chapter 7: IMS-4000 Sensors
139
• ConsoleView version 3.0.15 or higher
• IMS4K OS version 3.00 or higher
• Voice version 2.12 or higher
*Host version information is viewable through the ConsoleView software on the Version Info
screen and the Help>About selection from the main menu.
IMS-4000 Node
• Firmware version 2.59 or higher on Nodes with 10Mbit Ethernet ports.
• Firmware version 3.13 or higher on Nodes with 100Mbit Ethernet ports.
*Node version information is viewable through the ConsoleView software on the Node
Properties>Diagnostics screen.
Mounting
The sensor can be mounted to a wall or lie flat on the floor. To mount the sensor to a wall, install
four drywall anchors (if necessary) and attach the Current Sensor using four #6 tapping screws.
6.732
2.166
Figure 2: Mounting the sensor
Configuration
All IMS Solution sensors are auto-configured when you plug them into the Host or Node. The 15A
Current Sensor will identify itself as a 4-20mA transducer. On the Properties screen for this sensor
you must select the sensor type: Current Sensor. When a sensor is removed, or the connection is
disrupted, the configuration data remains intact but the sensor will go into trouble status and gener-
ate a trouble alarm. When the sensor is plugged in again, or the connection is re-established, con-
figuration data remains unchanged and the sensor returns to normal operating condition.
Caution
:Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.