background image

www.senjusprinkler.com

Document No. U028837 • 01-26-2022

Page 3 of 8 

The Model ZN-RES Residential Flush Pendent Sprinklers must only be installed and utilized in accordance with the 
following described criteria, which are provided by the manufacturer.

D E S I G N   C R I T E R I A

Figure 2:

 Operation Process (For illustrative purposes only)

Normal Condition         Sprinkler Operation         Water Discharge

Notes

Residential Fire Sprinkler Systems should only be designed and installed by those component and completely familiar with 
automatic sprinkler system design, installation procedures, and techniques.

Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the sprinkler 
system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the 
sprinkler system.

Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions, should be 
submitted to your contracted company. Include sketches and technical details, as appropriate.

In some instances, the requirements of this document may concern specifications which are more stringent and which take 
precedence over those specified in NFPA 13, NFPA 13D, NFPA 13R, or by the authority having jurisdiction.

The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently, the 
sprinklers must be located such that there will not be any blind spaces shielded from spray by partitions, room dividers, 
overhangs or other parts of the dwelling structure.

The number of sprinklers within each compartment (as defined by NFPA 13D, 13R, or 13) must be kept as few as possible while 
observing all guidelines relating to obstructions and spacing.

Use only the escutcheon provided with the Model ZN-RES. The sprinkler must be secured in position by firmly fastening 
the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from 
sprinkler operation could alter its orientation and its water distribution pattern.

The sprinkler escutcheon cannot be used to hold the sprinkler in position.

Obstruction to Water Distribution

Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers.

General Service Conditions

The Model ZN-RES must only be utilized in wet pipe sprinkler systems.

Heat Source Criteria

Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive 
Element of Model ZN-RES, due to the exposure of a heat source other than an actual fire.

Содержание ZN-RES

Страница 1: ...esidual pressures enabling smaller pipe sizes and water supply requirements The flush design of the Model ZN RES features a separable escutcheon providing 3 8 inch 9 5 mm vertical adjustment This adjustment reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut to help assure a perfect fit installation The Model ZN RES has been designed with heat sensitivity and water dis...

Страница 2: ...jurisdiction for guidance and approval It is the responsibility of the installing contractor to provide a copy of this document to the owner or their representative and in turn it is the obligation of the owner to provide a copy of this document to a succeeding owner The owner is responsible for maintaining their fire protection system and devices in proper operating condition The installing contr...

Страница 3: ...ed in NFPA 13 NFPA 13D NFPA 13R or by the authority having jurisdiction The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector Consequently the sprinklers must be located such that there will not be any blind spaces shielded from spray by partitions room dividers overhangs or other parts of the dwelling structure The number of sprinklers within each ...

Страница 4: ...m the most hydraulically demanding sprinkler from each of the total number of design sprinklers as specified in NFPA 13D or 13R For systems designed to NFPA 13 the number of designed sprinklers is to be the four most hydraulically demanding sprinklers The minimum required discharge from each of the four sprinklers is to be the greater of the followings The flow rates given in Table A for NFPA 13D ...

Страница 5: ... so that the distance from the face of the fitting to the mounting surface will be nominally 1 inch 25 0mm for Short body and 1 5 32 inch for Regular body as shown in Figure 3 Step 3 With pipe thread sealant applied to the pipe threads hand tighten the Sprinkler into the sprinkler fitting Sprinkler Spacing Criteria The minimum spacing between sprinklers is 8 feet 2 4m The maximum spacing between s...

Страница 6: ... as necessary If desired the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Cap Step 6 After the ceiling has been completed with the 2 inch 50mm diameter clearance hole use the Protective Cap Removal Tool Ref Figure 5 to remove the Protective Cap and then push on the Escutcheon until its flange just ...

Страница 7: ...y brushing with a feather duster or gently vacuuming with a soft bristle i e dusting brush attachment Exercise suitable safety precautions in the use and storage of highly flammable materials The rapid rate of fire development and spread of which can be caused by such materials can reduce the ability of the sprinkler system to aid in the control of a fire in which they are involved Sprinklers whic...

Страница 8: ...ecommended that automatic sprinkler systems be inspected tested and maintained by a qualified Inspection Service in accordance with NFPA 25 When placing an order please contact a local distributor with the following information Model Name Temperature and Finish Sprinkler Model ZN RES SIN SS4421 Residential Flush Pendent Sprinkler K4 2 Temperature 162 F 72 C or 175 F 79 C Finishes White Painted Bla...

Отзывы: