Senju Sprinkler ZN-QR Скачать руководство пользователя страница 5

www.senjusprinkler.com

Document No.U029423 • 01-06-2022 

Page 5 of 6 

Step 4: 

Wrench tighten the Sprinkler using only the Socket 

VC-H or Ratchet (3/8

 drive) & Socket VC-H Combination (Ref. 

Figure 4). The wrench recess of the Socket is to be applied to 
the sprinkler wrenching area (Ref. Figure 4).

Step 5: 

Use the “tolerance limit of ceiling level” indicator on the 

Protective Cap to check for proper installation height (Ref. Figure 3). 
Relocate the sprinkler fitting as necessary. If desired the Protective 
Cap may also be used to locate the center of the clearance hole by 
gently pushing the ceiling material against the center point of the Cap.

Step 6: 

After the ceiling has been completed with the 2-inch (50mm) diameter clearance hole, use the Cap Removal Tool 

(Ref. Figure 5) to remove the Protective Cap and then push on the Escutcheon until its flange just comes in contact with 
the ceiling (Ref. Figures 6 & Figure 7).

Figure 4:

 Ratchet & Socket

Figure 5:

 Protective Cap Removal

Figure 6: 

Installation

Figure 7:

 Installation (Correct and Incorrect)

Do not continue to push on the Escutcheon such that it lifts a ceiling panel 
out of its normal position. If the Escutcheon cannot be engaged with the 
Sprinkler, or the Escutcheon cannot be engaged sufficiently to contact the 
ceiling, relocate the sprinkler fitting as necessary.

Socket VC-H

Ratchet

Protective Cap

Wrenching Area

Protective Cap

Cap Removal Tool

Groove of Cap

Step 1

Step 2

L

o

L

o

Pull down

Mounting Surface

3″ (75 mm)

Escutcheon

Correct

Escutcheon

Mounting Surface

Mounting Surface

Escutcheon

Incorrect                                          Incorrect

There must 

not be space

Escutcheon and Frame

not be engaged

Frame