Document No.U086951

     

Date

Jan/11/2019 

NOTES 

Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with 
automatic sprinkler system design, installation procedures, and techniques. 
Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the 
sprinkler system designer review and develop a working understanding of the complete list of criteria prior to 
initiating the design of the sprinkler system. 
Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions, 
should be submitted to your contracted company. Include sketches and technical details, as appropriate. 
In some instances, the requirements of this document may concern specifications which are more stringent, and 
which take precedence over those specified in NFPA 13 or by the authority having jurisdiction. 
The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently, 
the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, 
overhangs or other parts of the dwelling structure. 
The number of sprinklers within each compartment (as defined by NFPA 13) must be kept as few as possible. Do NOT 
use more sprinklers than necessary to cover a particular space. 
The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure. If the sprinkler 
is not properly secured in position, reaction forces resulting from sprinkler operation could alter its orientation and its 
water distribution pattern. 
 

Obstruction to Water Distribution 

Locations of sprinklers must follow the obstruction rules of NFPA 13. 
 

General Service Conditions 

The Model FR-QR must only be utilized in sprinkler systems per NFPA 13 guidelines. 
 

Operational Sensitivity Criteria 

For proper operational sensitivity, the Model FR-QR Recessed Pendent Sprinklers must be installed beneath a solid ceiling 
having a smooth or textured surface. 
 

Heat Source Criteria 

Refer to NFPA 13 for the requirements relating to the prevention of possible activation of the Heat Responsive Element of 
Model FR-QR, due to the exposure of a heat source other than an actual fire. 
 

Precautionary Warnings for Corrosive Environments 

Model FR-QR sprinklers should not be installed where they may be subjected to a corrosive environment including the 
following: 

(1) Chlorine ion and Chloride environment. 

Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this 
environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire. 

(2) Sprinkler system piping with Copper. 

Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper piping 
when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper 
Development Association) – Solder Joint) 
All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before installation 
of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and leakage in the sprinkler system. 

 
 
 
 
 
 
 
 
 
 
 
 

Содержание FR-QR

Страница 1: ...as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction In the event of this condi...

Страница 2: ...Page 2 of 9 Document No U086951 Date Jan 11 2019 FIGURE 1 Model FR QR K5 6...

Страница 3: ...s Quick Response Sprinklers 3 Listed by UL for use in Canada as Quick Response Sprinklers 4 Approved by FM as Quick Response Sprinklers OPERATION The sprinkler assemblies fusible link is comprised of...

Страница 4: ...sition reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern Obstruction to Water Distribution Locations of sprinklers must follow the obstr...

Страница 5: ...t the position Installing Procedure Install Model FR QR sprinklers by the steps and figures shown below Use only D1 or D2 Recessed Escutcheons with Model FR QR Pendent sprinklers Use of any other rece...

Страница 6: ...Page 6 of 9 Document No U086951 Date Jan 11 2019 FIGURE 3 UPRIGHT PENDENT and RECESSED PENDENT SPRINKLERS FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH...

Страница 7: ...e 7 of 9 Document No U086951 Date Jan 11 2019 FIGURE 6 PROTECTOR REMOVAL FIGURE 7 INSTALLATION SOCKET A 1 2 drive ratchet not included is required for use with the Socket FR H FIGURE 8 PROTECTOR REMOV...

Страница 8: ...preparation for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be i...

Страница 9: ...and the regulations of any other authorities having jurisdiction The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufac...