The module is designed to exchange data according to the modes defined by the MODBUS protocol. It has a 

micro USB connector and can be configured using applications and/or software programs. The USB serial port 

uses the following communication parameters: 

115200,8,N,1

 

The USB communication port responds exactly like the  RS485 or RS232 ports with the exception of the 

communication parameters.

EASY SETUP is the software to use for the configuration.

For further information go to the following website:

www.seneca.it/products/ze-4di-2ai-2do - www.seneca.it/products/z-4di-2ai-2do - www.seneca.it/products/ze-2ai

Check that the device in question is included in the list of products supported by the Easy Setup APP in the store.

5/8

Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or 

the Z-PC-DINAL-17.5 accessory.

RS485 GND

 

RS485 A

 

RS485 B

 

Power Supply AC / +

 

Power Supply  AC / -

IDC 10

Back connector (IDC 10)

The illustration shows the meanings of the various 

IDC10 connector pins if signals are to be sent via 

them directly.

Power Supply AC

Ground

Power Supply AC

GNDSHLDG

ND

CANL

 / B

CAN

L / A

DI

SWITCH

Z-PC-DINAL2-17.5 accessory use

If the Z-PC-DINAL2-17.5 accessory is used, signals 

can be sent via terminal boards. The illustration 

shows the meaning of the various terminals and 

DIP-switch position (found in all supports for the DIN 

rail listed in Accessories) for the termination of the 

CAN network (not used for the Modbus network). 

GNDSHLD: 

Connection cable signal protection shield 

(recommended).

Android APP 

configuration

PC software 

configuration

Содержание ZE-4DI-2AI-2DO

Страница 1: ...visit www seneca it products ze 4di 2ai 2do www seneca it products z 4di 2ai 2do www seneca it products ze 2ai EN MI00543 0 EN 1 8 ZE 4DI 2AI 2DO Z 4DI 2AI 2DO ZE 2AI This document is the property of SENECA srl Copies and reproduction are prohibited unless authorised The con tent of this document corresponds to the described products and technologies Stated data may be modified or supplemented for...

Страница 2: ...F 4V ON 8V max 24 Vdc Current input 20mA Max frequency 5 KHz Absorbed current 3mA 12Vdc 10mA 24Vdc COUNTERS only ZE 4DI 2AI 2DO Z 4DI 2AI 2DO 4 x 32 bit resettable counters on non volatile memory DIGITAL OUTPUTS only ZE 4DI 2AI 2DO Z 4DI 2AI 2DO Number of channels 2 SPDT free contact relay Max voltage 250 Vac Max current 2A ANALOGUE INPUTS Number of channels 2 Configurable mAdc or Vdc Voltage inpu...

Страница 3: ...Union and other countries with recycling The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste The module must be repaired and damaged parts replaced by the Manufacturer The product is sensitive to electrostatic discharges Take appropriate measures during any operation SETTING THE DIP SWITCHES T...

Страница 4: ...g ducting or other objects that obstruct the ventilation slots Avoid mounting modules over heat generating equipment Installation in the bottom part of the electrical panel is recommended Insertion in the DIN rail As shown in figure 1 Insert the IDC10 rear connector of the module on a free slot of the DIN rail the insertion is univocal since the connectors are polarized 2 To secure the module to t...

Страница 5: ...oducts supported by the Easy Setup APP in the store 5 8 Power supply and Modbus interface are available using the Seneca DIN rail bus via the IDC10 rear connector or the Z PC DINAL 17 5 accessory RS485GND RS485A RS485B Power Supply AC Power Supply AC IDC 10 1 Back connector IDC 10 The illustration shows the meanings of the various IDC10 connector pins if signals are to be sent via them directly Po...

Страница 6: ...upply is connected to terminals 2 and 3 The supply voltage must be between 11 and 40Vdc indifferent polarity or between 19 and 28 Vac The power supply source must be protected from any failures in the module by means of a suitably sized fuse Power supply Power supply Auxiliary voltage 12 Vdc a 3 mA ANALOGUE INPUTS DIGITAL INPUTS ONLY ZE 4DI 2AI 2DO and Z 4DI 2AI 2DO DIGITAL OUTPUTS ONLY ZE 4DI 2AI...

Страница 7: ...Green ON Module powered and IP address acquired IP PWR Green Flashing Module powered and IP address not yet acquired or ETH port not connected Tx Rx Red Flashing Transmission and reception of data on at least one Modbus port port 1 RTU port 2 RTU ETH TRF Green Flashing Packet transmission on Ethernet port ETH LNK Yellow ON Ethernet port connected DI1 DI2 DI3 DI4 Red On Off Status of digital input ...

Страница 8: ...N At least one of the two analogue inputs is out of scale underscale overscale ETH TRF Green Flashing Packet transmission on Ethernet port ETH LNK Yellow ON Ethernet port connected Tx1 Red Flashing Modbus packet transmission from device to port 1 RTU Rx1 Red Flashing Modbus packet transmission to port 1 RTU Tx2 Red Flashing Modbus packet transmission from device to port 2 RTU Rx2 Red Flashing Modb...

Отзывы: