Power voltage must be in a range from 10 to 40 V     (indifferent 
polarity), from 19 to 28 V   ; see also section 

 

INSTALLATION

NORMS.
Upper limits must not be   exceeded, if it happen there could be 
damages for module

.

It is necessary to protect power source from possible module's 
failure by fuse correctly dimentioned.

ELECTRICAL CONNECTIONS

INPUT

2 3

19-40Vcc
19-28Vca

POWER

mA

7 8 9

I

mA

7 8 9

I

ACTIVE  INPUT

:  use  this  connection  with  transducers  2  wires 

technology.
Transducer  is  directly  powered  by  Z109S  module  20V      stabilized 
voltage, 20mA max., protected against short circuit.

PASSIVE INPUT

 : use this connection if input current is given from 

external (loop power  supply is given from external).

10-40V
19-28V

EN61000-6-4 (electromagnetic compability, industrial 
environment)
EN61000-6-2 (electromagnetic immunity, Industrial 
environment)
EN61010-1 (security)
Notes: - Use with copper conductor.
- Use in Pollution Degree 2 Environment .
- Power Supply must be Class 2.
- When supplied by an Isolated Limited Voltage/Limited 
   Current power supply a fuse rated max 2.5 A shall be 
   installed in the field.

Standards:

Complying equipments with prescriptions: