MI003161-E
ENGLISH - 1/4
Z109S-1
POWER-SUPPLY PLUS GALVANIC SEPARATION
FOR CURRENT LOOP
Input current 0 - 20 mA or 4 - 20 mA.
Sensors supply in two wires technique: 20V stabilized, 20mA max
protected against short circuit.
Measure and retransmission or an analog insulated output, current
output 0 - 20 mA or 4 - 20 mA.
Frontal power supply presence indicator.
Insulation 3 wires: 1500V .
GENERAL FEATURES
TECHNICAL FEATURES
EN
Protection
Output / Power-supply:
Against surge pulses 400W/ms
Inputs protection:
30V continuously.
Response time:
<200us, cutoff frequency (-3dB) 6kHz
Connections:
Removable 3-way screw terminals, 5 mm pitch.
cable section's 0.25-2.5 mm²
Errors referred to
Input’s measure range:
Calibration Thermal coeff. EMI
0,2% 0,02%/°C <1%
Environemental conditions:
Temperature:
Humidity:
Storage temperature:
Protection degree:
From -20 to +60 °C.
min: 30%, max 90% at 40°C not condensing
From -20 to +85 °C
IP20
(see also section
.
How to install)
10 - 40 V , 19 - 28 V 50 - 60Hz, max 2.5W.
Current 0 - 20 mA or 4 - 20 mA, 20Vdc
stabilized loop supply, input impedance 20 ohm.
Current 0-20 mA or 4-20 mA, loop impedance < 600 ohm.
Output:
Input:
Power:
Box
:
specification
Dimensions and weight:
Material:
100 x 112 x 18 mm, 130 g.
PBT, Black color.