background image

ANALOGUE INPUTS

Voltage

Active sensor current 

(4 wires)

Passive sensor current (2 wires)

(*) Not available without external power supply

The module has two 

analogue inputs that 

can be configured via 

software as voltage 

or current. For the 

configuration software, 

see the user manual.

5/6

ELECTRICAL CONNECTIONS

Power supply

Terminals 2 and 3 can be used to provide the module with power supply as an 

alternative to the connection using the Z-PC-DINx bus.

The power supply voltage must remain in the range of either 19 and 40V DC (any 

polarity), or 19 and 28V AC.

The upper limits must not be exceeded as this can seriously damage the module

.

If the power supply source is not protected against overload, a safety fuse with a 1 A 

max permissible value must be installed in the power supply line.

Serial port 2: RS485 SW2 = OFF

Z-LTE has a serial port that can be set with the SW2 switch.

If switch SW2 is in the OFF position, the RS485 COM 2 port is available at terminals 

10-11-12. The illustration shows how to complete connections.

N.B.: the indication of the RS485 connection polarity is not standardised and in some 

devices may be inverted.

1

2

3

10

11

12

Serial port 2: RS232 SW2 = ON

Z-LTE has a serial port that can be set with the SW2 switch.

If switch SW2 is in the ON position, the RS232 COM 2 port is available at terminals 

10-11-12.

The illustration shows how to complete connections.

The RS232 interface is fully settable.

10

11

12

GND

A (+)

B (-)

GND

RX

TX

Aux. volt. 

Vac/Vdc

Vac/Vdc

CAUTION

On first start-up the module must be supplied without any interruptions for at least 72 hours to charge the internal 

batteries. Switch the module off with the PS1 button before connecting inputs and outputs.

To meet the electromagnetic immunity requirements:

- use shielded signal cables;

- connect the shield to a preferential instrumentation earth system;

- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc...).

+

+

+

+

DIGITAL INPUTS

NPN with internal power

PNP with internal power

PNP with external power