TECHNICAL SPECIFICATIONS
ENGLISH - 2/8
STANDARDS
EN61000-6-4
Electromagnetic emissions, industrial environment.
EN61000-6-2
. Electromagnetic immunity, industrial environment.
EN60950 -1
Safety.
INSULATION
ENVIRONMENTAL
CONDITIONS
-20°– + 65°C
30%– 90% non condensing.
-20 – + 85°C
IP20.
Temperature
Humidity
Storage temperature
Protection rating
ASSEMBLY
25Mm DIN rail IEC EN60715
CONNECTIONS
Removable 3-way screw terminals, 5 mm pitch for cable up to 2.5
mm2, IDC10 Rear, RJ45 and micro USB.
POWER SUPPLY
11 – 40 Vdc or 19 – 28 Vac ; 50 – 60 Hz. P typ. 3.5W P 6.5 W max.
EXTERNAL MEMORY
Side slot for micro SD card
COMMUNICATIO
N PORTS
Rear RS485 COM1 IDC10. RS485 or RS232 M10-M11-M12.
Ethernet 10/100 baseT RJ45 front with autoswitch.
Side micro USB.
PROTOCOLS
MeterBUS, ModBUS TCP server and ModBUS RTU
slave.
For further information, refer to the
User Manual
.
PROCESSOR
ARM 32bit.
FEATURES
Integrated webserver, Number of MBUS slave 25 max.
t
1500 V
A
POWER SUPPLY
RS485
RS232
MeterBUS
2 3
24
22
...
IDC10 RJ45 USB
10
11
12
MBus PORT (Meter-Bus) on terminals M22-M24
Number of slaves: 25 Max.
Baud rate: 300 - 38k4 Baud
Voltage: 28 Vdc
Maximum length: 3000 m