ENGLISH 4/8

MI003630-E

Inserting in the DIN rail 

How the picture shows:  

1) Insert the IDC10 connector in the rear of the 
module  on  the  DIN  rail  free  slot  (inserting  is 
univocal because  connectors are polarized).

2) The  module  can  be  fixed  on  the  DIN  rail  by 
pressing the two hooks located on the rear of the 
module.

INSTALLATION RULES

The module is designed to be installed, in vertical position, on DIN rail complies with the 
standard  IEC  EN  60715.    For  the  best  module  performance  and  long  life,  avoid  to
place  cables  raceways  and  other  objects  that  could  obstruct  ventilation  slits.
Never install the modules near heat sources. We suggest to install the module in the bottom 
of the control panel.

NOTE: 

In  order  to  obtain  maximum  performances  it’s  recommended  to  use  a  specific 

shielded cable, as an example BELDEN 9841.

Scheme 1

Bus

Length

Drop

Lenght

1200 m

2 m

MODBUS CONNECTIONS RULES

1)  Connect the module into the 

 IEC EN 60715

)

DIN rail

 (max 120

2)  Please use cables with a suitable length to connect the remote modules.
The following table contains information data on the allowed cable lengths:
-Bus Length: MODBUS Maximum  bus length depending on the Baud Rate.
It defines the connection length between two modules that have the bus terminator
 DIP-switch switched ON. (see scheme 1).
-Drop Lenght: Maximum lenght of branch (see scheme 1).

Inserting on the

omega DIN rail

IEC EN 60715

omega
DIN rail

Содержание Z-4TC-1

Страница 1: ...stria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals and configuration software please see www seneca it Contents General specifications Technical features Modbus connections rules Installation rules Electrical connections DIP switches settings Main MODBUS registers LED signallings Purchase order codes Factory settings Module layout Decommissioning and disposal Ins...

Страница 2: ...easurement C by thermocouples type J K E N S R B T Up to 4 inputs for voltage measurement mV Voltage or thermocouple inputs with 16 bit resolution 1500 V isolated inputs compared with other low voltage circuits Easy connections for power supply and serial communication by seneca bus that can be mounted on standard DIN rail IEC EN 60715 2 Removable terminals with section of 2 5 mm RS485 serial comm...

Страница 3: ... Power supply 9 10 7 8 IDC10 Jack IDC10 11 12 4 5 6 2 3 RS232 Analog Inputs Dimensions Box Dimensions L 100 mm H 112 mm W 17 5 mm Box PA6 Black Connections Power supply Inputs RS485 Removable 3 way screw terminals 5 08 pitch RS485 Interface IDC10 connector for DIN rail complies with IEC EN 60715 terminals 4 5 and 6 Frontal jack 3 5 mm RS232 Interface Environmental condition Temperature 10 65 C Hum...

Страница 4: ... the modules near heat sources We suggest to install the module in the bottom of the control panel NOTE In order to obtain maximum performances it s recommended to use a specific shielded cable as an example BELDEN 9841 Scheme 1 Bus Length Drop Lenght 1200 m 2 m MODBUS CONNECTIONS RULES 1 Connect the module into the IEC EN 60715 DIN rail max 120 2 Please use cables with a suitable length to connec...

Страница 5: ...the connection cables against interferences recommended The picture shows the meaning of the I D C 1 0 c o n n e c t o r p i n s T h i s connector can be used as alternative to the screw terminals blocks Rear connector IDC10 RS485 GND Power Supply AC RS485 A RS485 B Power Supply AC IDC 10 1 2 3 19 28 V 50 60 Hz 10 40 V 1 W Max Power supply The supply voltage must be between 10 and 40 V Any polarit...

Страница 6: ...Connection for RS485 communication with the Modbus Master system as an alternative to Z PC DINx bus Note the indication of RS485 connection polarity is not standard it may be inverted on some masters 4 GND 5 B 6 A Tc type Range Linearization error Tc type Range Linearization error J 210 C 1200 C 0 05 C S 50 C 1768 C 0 02 C K 200 C 1372 C 0 05 C R 50 C 1768 C 0 02 C E 200 C 1000 C 0 02 C B 250 C 18...

Страница 7: ...in OFF comunication settings are recovered from EEprom 2nd Note The termination of RS485 communication must be enabled only to the ends of the communication line DIP SWITCHES SETTING DIP Switches must be set when module is powered down otherwise the module may be damaged The DIP switches positions define the Modbus communication parameters Address and Baud rate In the following table the Baud rate...

Страница 8: ...ycling of the product please contact your local city office waste disposal service of the retail store where you purchased this product Variations of standard parameters are possible by using configuration softwares Z NET or EASY Z PC available at www seneca it site For more information about a list of all register and their function please see the USER manual 1 2 3 4 5 6 7 8 9 10 11 12 S Z 4TC PW...

Отзывы: