background image

MI00360-2-EN

INSTALLATION MANUAL

2/4

CERTIFICATIONS

https://www.seneca.it/products/z-4ai/doc/CE_declaration

INSULATION

ENVIRONMENTAL 

CONDITIONS

Temperature:

 

-10 ÷ + 65°C

Humidity:

 

30% ÷ 90% non condensing.

Altitude: 

Up to 2000 m above sea level

Storage temperature:

  -20 ÷ + 85°

Protection rating: 

IP20.

ASSEMBLY

IEC EN60715, 35mm DIN rail in vertical position.

CONNECTIONS

3-way removable screw terminals, pitch 5 mm

Rear connector IDC10 for DIN bar 46277

front micro USB

POWER SUPPLY

Voltage: 10 ÷ 40Vdc; 19 ÷ 28Vac 50 ÷  60Hz

Absorption: Typical: 0.5W @ 24Vdc, Max: 3.5W

MODULE LAYOUT

Dimensions LxHxD:

 17.5 x 102.5 x 111 mm; 

Weight:

 110 g; 

Enclosure:

 PA6, black

17.5 mm

111
 m

m

102.5 mm

LED

STATUS

LED meaning

PWR Green

ON

The device is powered correctly

FAIL yellow

Flashing

Anomaly or fault

RX Red

Flashing

Receipt of packet completed

RX Red

ON

Anomaly / Check connection 

TX Red

Flashing

Transmission of packet completed

SIGNALS VIA LED ON FRONT PANEL

TECHNICAL SPECIFICATIONS

Power

Supply

Analog

Input

Comm.

1500 V

~

mA / V

mA / V

mA / V

mA / V

RS485

WARNING

the maximum working voltage between any 

terminal and ground must be less

 

than 50Vac / 75Vdc

Содержание Z-4AI

Страница 1: ...ake appropriate measures during any operation PRELIMINARY WARNINGS The word WARNING preceded by the symbol indicates conditions or actions that put the user s safety at risk The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment The warranty shall become null and void in the event of improper use or tampering with the m...

Страница 2: ...POWER SUPPLY Voltage 10 40Vdc 19 28Vac 50 60Hz Absorption Typical 0 5W 24Vdc Max 3 5W MODULE LAYOUT Dimensions LxHxD 17 5 x 102 5 x 111 mm Weight 110 g Enclosure PA6 black 17 5 mm 111 mm 102 5 mm LED STATUS LED meaning PWR Green ON The device is powered correctly FAIL yellow Flashing Anomaly or fault RX Red Flashing Receipt of packet completed RX Red ON Anomaly Check connection TX Red Flashing Tra...

Страница 3: ... 1 to 4 VOLTAGE 10 Vdc Numerical representation of the input measurement 10000 mV Sampling time 120 ms 1200 m 2 m 2 1 4 5 Ld Diagram 1 Bus length Derivation length Module Module Module Module Module 3 Bus length Ld derivation length ModBUS CONNECTION RULES 1 Install the modules in the DIN rail 120 max 2 Connect the remote modules using cables of an appropriate length The following table shows cabl...

Страница 4: ...overload a safety fuse with a 2 5A max permissible value must be installed in the power supply line GND B A 4 5 6 ModBus RS485 ConnectionforRS485communicationusingtheMODBUSmastersystemasanalternative to the Z PC DINx bus N B The indication of the RS485 connection polarity is not standardised and in some devices may be inverted INPUTS A Voltage input with sensor supply from the MODULE 13 Vdc B Volt...